2018-06-03 09:41:40 | 1) THE SUBMITTED GAS PLAN SHOWS AN EXISTING 3/4 INCH |
| GAS LINE FROM THE METER SUPPLYING AN 1 1/4 INCH |
| GALVANIZED. PROVIDE ADDITIONAL DETAILS AS TO HOW THIS |
| FEAT WILL BE ACCOMPLISHED.THE EXISTING PLANS ON FILE |
| SHOW AN 1 1/2 INCH GALVANIZED PIPE AT THE METER. |
| 2) THE SUBMITTED GAS PLAN SHOWS A 12 INCH WATER COLUMN |
| NATURAL GAS METER BUT THERE IS ALSO A NOTE STATING IT |
| IS A 2 PSI SYSTEM. WHICH IS IT? CLARIFY. |
| 3) SHOW THE DISTANCE FROM THE OUTLET OF THE GAS METER |
| TO THE MOST REMOTE GAS OUTLET INTO THE STRUCTURE AND |
| THE LOAD ON THAT SECTION.2017 FBCR SEC. G2413.4.1. THE |
| EXISTING PLANS ON FILE WITH THE CITY SHOW A DISTANCE OF |
| 200 FEET FROM THE METER TO THE FURTHEST OUTLET ON THE |
| SYSTEM WHICH IS THE POOL HEATER. THIS DISTANCE SHALL BE |
| USED FOR THE SIZING OF THIS SYSTEM. |
| 4) THE MINIMUM SIZE SCH. 40 METALLIC PIPE AT THE METER |
| SHALL BE 2 1/2 INCHES PER THE TOTAL BTU LOAD AND THE |
| DISTANCE FROM THE METER TO THE MOST REMOTE OUTLET.2017 |
| FBCR SEC. G2413.4.1, TABLE G2413.4 (1). |
| 5) IF THIS IS A LOW PRESSURE SYSTEM, WHY ARE YOU |
| SUBMITTING SPECS FOR REGULATORS? CLARIFY. |
| 6) IF THIS IS GOING TO BE A 2 PSI SYSTEM SUBMIT THE |
| APPLICABLE SIZING TABLE FOR THE SYSTEM AND SHOW THE |
| DISTANCE FROM EACH MP REGULATOR TO THE FURTHEST OUTLET |
| AND BTU LOAD ON THAT SECTION. 2017 FBCR SEC. G2413.4.1. |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| PLUMBING PLAN REVIEW |
| 561-805-6692 |
| |