Plan Review Notes
Plan Review Notes For Permit 18050024
Permit Number 18050024
Review Stop G
Sequence Number 1
Notes
Date Text
2018-05-14 05:55:121) SHOW THE TYPE OF PIPE AND PIPE SIZE AT THE OUTLET OF
 THE 12" W.C.GAS METER . WPB AMEND. TO FBC SEC.
 107.2.1.THE SIZE OF THE PIPE SHALL COMPLY WITH 2017
 FBC-FUEL GAS FOR THE TOTAL BTU LOAD ON THE SYSTEM. 2017
 FBC-FUEL GAS SEC.401.3, 401.4.
 2) SHOW THE PIPE SIZE OF THE SECTION OF PIPE SERVING
 THE EXISTING GAS LOAD.WPB AMEND. TO FBC SEC. 107.2.1.
 3) SHOW THE DISTANCE FROM GAS METER TO THE FURTHEST
 EXISTING OUTLET ON THE SYSTEM. THE GAS PLAN NOTES
 LONGEST RUN AS 10 FT. SHOW THIS ON THE DRAWING. DOES
 THIS INCLUDE THE FURTHEST OUTLET FROM THE METER ON THE
 EXISTING SYSTEM? CLARIFY ON THE PLANS. WPB AMEND. TO
 FBC SEC. 107.2.1.
 4) SPECIFY ON THE GAS DRAWING HOW THE 1 INCH GALVANIZED
 PIPE IS GOING TO BE INSTALLED. ABOVE-GROUND PIPING
 OUTDOORS SHALL COMPLY WITH 2017 FBCR SEC.G2415.9,
 G2415.11.
 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FLEX
 CONNECTOR FOR THE GENERATOR. THE FLEX CONNECTOR SHALL
 BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE
 GENERATOR. 2017 FBCR SEC. G2422.1 (8).
 7) THE SEDIMENT TRAP AS DRAWN DOES NOT COMPLY WITH 2017
 FBCR SEC.G2419.4.
 8) IF THE TOTAL LOAD IS 806,000 BTU'S AT THE OUTLET OF
 THE GAS METER, THEN THE MINIMUM PIPE SIZE FROM THE
 METER SHALL BE A MINIMUM OF 1 1/4 INCH PER TABLE 402.4
 (2) DEPENDDING ON THE DISTANCE OF THE FURTHEST GAS
 OUTLET FROM THE GAS METER.
 9) LIST THE EXISTING GAS FIXTURES ON THE PLAN AND THE
 CORRESPONDING BTU LOAD FOR EACH APPLIANCE. WPB AMEND.
 TO FBC SEC .107.2.1, 2017 FBC-FUEL GAS SEC.402.1.
  
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  