2018-05-14 09:20:47PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE SPECIFICATIONS FOR THE GENERAC 22KW GENERATOR
 LISTS A UNIT WEIGHT OF 466 LBS. AND THE ENGINEER'S
 DRAWINGS FOR THE PAD REQUIRE A MINIMUM WEIGHT OF 526
 LBS. THEREFORE, THIS PAD CAN NOT BE USED WITH THIS
 GENERATOR. FBC-R 301.1
  