Plan Review Notes
Plan Review Notes For Permit 18050023
Permit Number 18050023
Review Stop G
Sequence Number 1
Notes
Date Text
2018-06-03 07:55:381) SHOW THE DISTANCE OF THE EXISTING GAS LINE FROM THE
 GAS METER TO THE FURTHEST GAS OUTLET ON THE SYSTEM.THE
 EXISTING PLAN ON FILE IN CITY RECORDS SHOWS 88 FEET TO
 THE FURTHEST OUTLET. THIS DISTANCE SHALL BE USED FOR
 SIZING THE PIPING FOR THE GENERATOR AND FOR THE CHEKING
 THE EXISTING SYSTEM.IF UNDERSIZED, THE EXISTING SYSTEM
 MUST BE REDONE TO ENSURE A SAFE OPERATING SYSTEM WPB
 AMEND. TO FBC SEC. 107.2.1,
 2) HOW DO YOU PLAN ON SUPPLYING AN 1 1/4 INCH LINE WITH
 A 3/4 INCH LINE AT THE OUTLET OF THE GAS METER? THE
 LINE AT THE OUTLET OF THE METER SHALL BE A MINIMUM OF 1
 1/2 INCHES AS SHOWN ON THE EXISTING PLAN ON FILE WITH
 THE CITY.
 3) THE EXISTING PLAN ON FILE WITH THE CITY ALSO SHOWS A
 FUTURE BBQ THAT NEEDS TO BE LISTED AND ADDED ON THE BTU
 LOAD OF THE SUBMITTED GAS PLAN.2017 FBCR SEC. G2412.3,
 G2412.4.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
  