Plan Review Notes For Permit 18050023 |
Permit Number |
18050023 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-06-03 07:55:38 | 1) SHOW THE DISTANCE OF THE EXISTING GAS LINE FROM THE | | GAS METER TO THE FURTHEST GAS OUTLET ON THE SYSTEM.THE | | EXISTING PLAN ON FILE IN CITY RECORDS SHOWS 88 FEET TO | | THE FURTHEST OUTLET. THIS DISTANCE SHALL BE USED FOR | | SIZING THE PIPING FOR THE GENERATOR AND FOR THE CHEKING | | THE EXISTING SYSTEM.IF UNDERSIZED, THE EXISTING SYSTEM | | MUST BE REDONE TO ENSURE A SAFE OPERATING SYSTEM WPB | | AMEND. TO FBC SEC. 107.2.1, | | 2) HOW DO YOU PLAN ON SUPPLYING AN 1 1/4 INCH LINE WITH | | A 3/4 INCH LINE AT THE OUTLET OF THE GAS METER? THE | | LINE AT THE OUTLET OF THE METER SHALL BE A MINIMUM OF 1 | | 1/2 INCHES AS SHOWN ON THE EXISTING PLAN ON FILE WITH | | THE CITY. | | 3) THE EXISTING PLAN ON FILE WITH THE CITY ALSO SHOWS A | | FUTURE BBQ THAT NEEDS TO BE LISTED AND ADDED ON THE BTU | | LOAD OF THE SUBMITTED GAS PLAN.2017 FBCR SEC. G2412.3, | | G2412.4. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | |
|