Plan Review Notes For Permit 18050016 |
Permit Number |
18050016 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-05-14 06:01:58 | | | 1) SHOW THE TYPE OF PIPE AND PIPE SIZE AT THE OUTLET OF | | THE 2 PSI METER . WPB AMEND. TO FBC SEC. 107.2.1. | | 2) SHOW THE PIPE SIZE OF THE SECTION OF PIPE TO THE | | REGULATOR SERVING THE EXISTING GAS LOAD.WPB AMEND. TO | | FBC SEC. 107.2.1. | | 3) SHOW THE TYPE OF PIPE AND PIPE SIZE DOWNSTREAM OF | | THE REGULATOR FOR THE EXISTING GAS LOADS AND NOTE THE | | DISTANCE FROM THIS REGULATOR TO THE FURTHEST OUTLET ON | | THAT SYSTEM.WPB AMEND. TO FBC SEC. 107.2.1. | | 4) A LISTED SHUTOFF VALVE IS REQUIRED IMMEDIATELY AHEAD | | OF THE MP REGULATOR FOR THE EXISTING LOADS.. 2017 FBCR | | SEC. G2420.4. | | 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FLEX | | CONNECTOR FOR THE GENERATOR. THE FLEX CONNECTOR SHALL | | BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE | | GENERATOR. 2017 FBCR SEC. G2422.1 (8). | | 6) THE SEDIMENT TRAP AS DRAWN DOES NOT COMPLY WITH 2017 | | FBCR SEC.G2419.4. | | 7) LIST THE EXISTING GAS FIXTURES ON THE PLAN AND THE | | CORRESPONDING BTU LOAD FOR EACH APPLIANCE. WPB AMEND. | | TO FBC SEC .107.2.1, 2017 FBC-FUEL GAS SEC.402.1. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | | | | | |
|