Plan Review Notes For Permit 18050006 |
Permit Number |
18050006 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-05-03 14:18:24 | FLORIDA BUILDING CODE 2017 6TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | NFPA 70 2014 EDITION | | | | JAKE LEAHY | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | | | 240.87 ARC ENERGY REDUCTION | | WHERE THE HIGHEST CONTINUOUS CURRENT TRIP SETTING FOR | | WHICH THE | | ACTUAL OVERCURRENT DEVICE INSTALLED IN A CIRCUIT | | BREAKER IS RATED | | OR CAN BE ADJUSTED IS 1200 A OR HIGHER, 240.87(A) AND | | (B) SHALL | | APPLY. | | (A) DOCUMENTATION. DOCUMENTATION SHALL BE AVAILABLE TO | | THOSE | | AUTHORIZED TO DESIGN, INSTA LL, OPERATE, OR INSPECT THE | | INSTALLATION | | AS TO THE LOCATION OF THE CIRCUIT BREAKER(S). | | (B) METHOD TO REDUCE CLEARING TIME. ONE OF THE | | FOLLOWING | | OR APPROVED EQUIVALENT MEANS SH ALL BE PROVIDED: | | (1) ZONE-SELECTIVE INTERLOCKING | | (2) DIFFERENTIAL RELAYING | | (3) ENERGY-REDUCING MAINTENANCE SWITCHING WITH LOCAL | | STATUS | | INDICATOR | | (4) ENERGY-REDUCING ACTIVE ARC FLASH MITIGATION SYSTEM | | (5) AN APPROVED EQUIVALENT MEANS |
|