2018-05-14 11:12:43 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) THERE IS NO DOCUMENTATION OF 61G REQUIRED |
| INFORMATION FOR THE MASTER PERMIT, 18050056, ASSOCIATED |
| WITH THIS PROJECT. |
| |
| WHAT INFORMATION WAS USED TO PROVIDE THESE DESIGNED |
| DRAWINGS? |
| |
| FAC 61G15-32.002 DEFINES THE FIRE PROTECTION SYSTEM |
| ENGINEERING DOCUMENT (5) AS WELL AS THE FIRE PROTECTION |
| SYSTEM LAYOUT DOCUMENT (6). 61G15-32.003 OUTLINES THE |
| COMMON REQUIREMENTS TO ALL FIRE PROTECTIONS ENGINEERING |
| DOCUMENTS WITH 32.004 (2) (A-J) OUTLINING THE MINIMUM |
| INFORMATION TO BE PROVIDED ON FIRE PROTECTION |
| ENGINEERING DOCUMENTS FOR WATER BASED SYSTEMS. AS |
| STATED IN THE DEFINITIONS, THE CONTRACTOR IS TO DEVELOP |
| THE LAYOUT DOCUMENTS BASED ON THE DESIGN CRITERIA |
| PROVIDED IN THE FIRE PROTECTION ENGINEERING DOCUMENTS |
| BY THE ENGINEER OF RECORD FOR THE FIRE SPRINKLER |
| SYSTEM. THE FIRE PROTECTION SYSTEM ENGINEERING |
| DOCUMENTS ARE SUBMITTED FOR THE MASTER PERMIT (BUILDING |
| PERMIT PER FBC) AND THE LAYOUT DOCUMENTS ARE SUBMITTED |
| FOR THE FIRE SPRINKLER INSTALLATION PERMIT. |
| |
| PLEASE CORRECT OR JUSTIFY. |
| |
| 2) THERE IS AN INDICATION OF A STAMP AND SEAL OF AN |
| ENGINEER ON THESE DRAWINGS. |
| |
| THERE CAN ONLY BE 1 ENGINEER OF RECORD |
| |
| FAC 61G15-32.002 DEFINES THE FIRE PROTECTION SYSTEM |
| ENGINEERING DOCUMENT (5) AS WELL AS THE FIRE PROTECTION |
| SYSTEM LAYOUT DOCUMENT (6). 61G15-32.003 OUTLINES THE |
| COMMON REQUIREMENTS TO ALL FIRE PROTECTIONS ENGINEERING |
| DOCUMENTS WITH 32.004 (2) (A-J) OUTLINING THE MINIMUM |
| INFORMATION TO BE PROVIDED ON FIRE PROTECTION |
| ENGINEERING DOCUMENTS FOR WATER BASED SYSTEMS. AS |
| STATED IN THE DEFINITIONS, THE CONTRACTOR IS TO DEVELOP |
| THE LAYOUT DOCUMENTS BASED ON THE DESIGN CRITERIA |
| PROVIDED IN THE FIRE PROTECTION ENGINEERING DOCUMENTS |
| BY THE ENGINEER OF RECORD FOR THE FIRE SPRINKLER |
| SYSTEM. THE FIRE PROTECTION SYSTEM ENGINEERING |
| DOCUMENTS ARE SUBMITTED FOR THE MASTER PERMIT (BUILDING |
| PERMIT PER FBC) AND THE LAYOUT DOCUMENTS ARE SUBMITTED |
| FOR THE FIRE SPRINKLER INSTALLATION PERMIT. |
| |
| PLEASE CORRECT OR JUSIFY |
| |
| |
| 3) THESE PLANS WILL NOT BE REVIEWED IN DETAIL UNTIL THE |
| ABOVE NOTED COMMENTS ARE CORRECTED OR APPLICABLY |
| JUSTIFY IN COMPLIANCE WITH FIRE CODE AND FLORIDA LAW. |
| |
| |
| |
| 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |
| 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |