Plan Review Notes
Plan Review Notes For Permit 18050001
Permit Number 18050001
Review Stop G
Sequence Number 3
Notes
Date Text
2018-06-18 13:03:101) THE GAS PLAN SHOWS 1 1/4 INCH AND 3/4 INCH PIPING
 AND THE SHEET YOU HAVE SUBMITTED FOR THE REGULATOR
 SHOWS AN INLET SIZE OF 3/4 INCH AND AN OUTLET SIZE OF 1
 INCH. CLARIFY.
 2) SHOW THE ORIFICE SIZE FOR THE REGULATOR BEING USED
 SO THE BTU LOAD CAN BE CHECKED.
 3) THERE ARE TWO DIFFERENT SETS OF GAS PLANS IN THIS
 SUBMITTAL. REMOVE ALL OLD DOCUMENTS AND SUBMIT ONLY TWO
 SETS OF PLANS FOR REVIEW. WPB AMEND. TO FBC SEC. 107.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]