2018-05-27 14:23:35****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID.
  
 1. FROM PREVIOUS LIST; NOT ADDRESSED. REVISE PLAN TO
 SHOW MEANS OF ESCAPE REQUIRED BY FBC R 310.4; INCLUDE
 ROOM DESIGNATION. IF APPEARS THAT THREE OPENINGS WILL
 BE LEFT OPEN BUT NOT CLEAR IF THEY ARE DOORS, WINDOWS,
 OR WHAT ROOM THEY ARE LOCATED IN (CANNOT BE A LOCKABLE
 ROOM).
  
 TWO ADDITIONAL FLOOR PLANS WERE PROVIDED BUT NO NEW
 INFORMATION.
  
 2. ONE INSTALATION SCHEDULE WAS SUBMITTED, TWO
 REQUIRED, FBC 107. THE INSTALLATION SCHEDULE LACKS THE
 SHUTTER CONNECTION TYPE PER PRODUCT APPROVAL; THIS
 SHOULD CORRELATE WITH THE DESIGN PRESSURE CHARTS. "TAP
 CON" WAS WRITTEN; THIS IS THE FASTENER. SEE SHEET 12,
 THE INFO THAT BELONGS IN THIS COLUMN SHOULD BE A OR D
 (WHAT WAS HIGHLIGHTED). FBC R 301.
  
 3. NOTE THAT ONE OF THE BOXES HIGHLIGHTED HAS A "-"
 RATHER THAN A NUMBER. THAT MEANS THIS IS NOT PERMITTED,
 ANOTHER OPTION MUST BE SELECTED.
  
 4. ORIENTATION IS NOTED AS "HORIZONTAL" BUT THE
 SHUTTERS PROPOSED ARE ACCORDIONS. ACCORDIONS ARE
 TYPICALLY INSTALLED VERTICALLY. PLEASE CONFIRM WITH
 QUALIFIER.
  
  
  
  