2018-11-02 07:05:27 | 1) THE PLAN DRAWING SHOWS A 30,000 LOG LIGHTER BUT IT | | IS NOT SHOWN ON THE GAS DRAWING. CLARIFY. | | 2) SHOW THE EHD OF THE 1/2 INCH CSST. | | 3) SUBMIT MANUF. SPECS FOR THE LOG LIGHTER IF IT IS TO | | BE INSTALLED. THE LOG LIGHTER SHALL BE LISTED AND | | LABELED. | | 4) THE 1 INCH PE PIPE SUPPLYING THE TWO TANKLESS WATER | | HEATERS IS UNDESIZED. IT MUST BE INCREASED TO 1 1/4 | | INCHES. PER 2017 FBC-FUEL GAS TABLE 402.4(16) THE | | MAXIMUM BTU LOAD AT 40 FEET IS 343,000 BTU'S. THE TWO | | WATER HEATERS TOTAL 370,000 BTU'S. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | |
|