2018-05-07 07:57:0005/07/2018 1ST GAS REVIEW**DENIED**
  
 1) PLANS THAT BEAR THE TILTE BLOCK OF A LICENSE
 ENGINEER REQUIRES PLANS TO BE SEALED AND SIGED PER FL
 ADMIN CODE 61G15-23.001
  
 2) SUPPLY TANKLESS INSTALLATION MANUAL SHOW MIN
 DISTANCE REQUIRED FROM A DOOR OR WINDOW THAT OPEN'S.
 SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
  
 3) SUPPLY WHAT APPROVING BODIES THE STOVE IS LISTED AND
 LABEL UNDER. GAS APPLIANCES SHALL BE LISTED AND
 LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
  
 4) THE PLAN SHOW TANKLESS WATER HEATER IN 3 DIFFERENT
 LOCATION'S FOR A TOTAL OF 4. YOUR PERMIT APPLICATION IS
 FOR 2 HWH. PLEASE REVISE PLAN TO CLEARIFY. FBC 107.2.1
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT