Plan Review Notes
Plan Review Notes For Permit 18041305
Permit Number 18041305
Review Stop P
Sequence Number 2
Notes
Date Text
2018-06-07 09:54:042ND REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS: PREVIOUS COMMENTS HAVE NOT BEEN
 COMPLIED WITH. 2ND REQUEST. NO RESPONSE LETTER WAS
 PROVIDE
  
 1. PLEASE PROVIDE WATER ISOMETRIC DRAWING. AMEND TO FBC
 107.3.5.1.3(3)(13)
  
 2. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA PER FBC PL 416.5 PROVIDE
 PIPING DETAIL
  
 3. IS THE WATER HEATER EXISTING IF NEW PROVIDE
 MANUFACTURE SPECS. PER AMEND TO FBC 107.2.1 PROVIDE
 PIPING DETAIL
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  