Plan Review Notes
Plan Review Notes For Permit 18041305
Permit Number 18041305
Review Stop B
Sequence Number 2
Notes
Date Text
2018-06-05 09:54:38SHELL ONLY, SECOND REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
  
  
 ORIGINAL COMMENT:
 1- PROVIDE ALL THE WIND DESIGN DATA AS REQUIRED BY SEC.
 1603.1.4 FBC.
  
 SEC. 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
 1.ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
 2.RISK CATEGORY.
 3.WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE THAN
 ONE WIND EXPOSURE IS UTILIZED.
 4.APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5.DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF
 (KN/M2).
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED. PLANS CALL FOR
 REPLACEMENT OF EXISTING STOREFRONT. ALL WIND DESIGN
 DATA IS REQUIRED. PLANS NEED TO BE CLEAR ON THE SCOPE
 OF WORK TO AVOID CONFLICTS/DELAYS. REVISE INFORMATION
 ON PLANS AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 2- A) PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED
 BY FAC 61G20-3.001 FOR THE NEW EXTERIOR DOOR #1.
  
 ORIGINAL COMMENT:
 B) DOOR #2 SHOWN ON FLOOR PLAN AT THE ENTRY DOESN'T
 MATCH DOOR SHOWN ON THE DOOR SCHEDULE ON SHEET 1.0A.
 REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 3- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 4- REVISE OCCUPANT LOAD NUMBER. NUMBER OF PEOPLE IS
 ROUNDED UP NOT ROUNDED DOWN. 3475 SF DIVIDED BY 100
 EQUALS 34.75. THEREFORE NUMBER OF PEOPLE IS 35. REVISE
 AS REQUIRED. TABLE 1004.1.2 FBC.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 5- SHEET 1.0A:
 A) PROVIDE ALL DIMENSIONS FOR RESTROOM LOCATED IN THE
 CENTER OF THE SPACE AND SHOW THE TURNING SPACE REQUIRED
 BY SEC. 603.2.1 FBC-ACCESSIBILITY.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]