2018-05-09 17:31:26 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #18041305 |
| 5/9/17 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| SOME OF THE COMMENTS BELOW ALSO APPEAR ON PERMIT |
| #18041229 BECAUSE THE PLANS ARE BOTH TITLED "VANILLA |
| SHELL BUILDOUT", THE APPLICATIONS SHOW THE SAME WORK |
| DESCRIPTION, AND BOTH PLANS SHOW THE SAME RTU |
| INSTALLATIONS. |
| |
| 1) REPLACEMENT OF THE AC SYSTEMS ARE NOT EXACT SAME |
| SIZE REPLACEMENTS SO COOLING AND HEATING CALCULATIONS |
| ARE REQUIRED TO VERIFY ACCURATE SIZING- SECTION |
| C403.2.1 FBC-14 ENERGY CONSERVATION. |
| |
| 2) SHEET C-1, NOTE 3 & SHEET 4.0M: SHOW THE LOCATIONS |
| OF THE ROOFTOP HOODS AND PROVIDE CAPPING DETAILS. |
| |
| 3) 4.0M: DUCT SMOKE DETECTORS ARE REQUIRED IN THE |
| SUPPLY SYSTEMS OF THE NEW 5-TON RTU'S , UNLESS |
| MANUFACTURER'S SPECIFICATIONS INDICATE THE SYSTEMS |
| CANNOT PRODUCE OVER 2000 CFMS OF SUPPLY AIR- SECTION |
| 606.2.1. |
| |
| 4) 4.0M: THE CONDENSATE PIPING SHALL BE SUPPORTED AT |
| MAXIMUM 4' INTERVALS- TABLE 305.4. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. |
| |