2018-05-09 14:20:37 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2017 6TH ED. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. RISER DIAGRAM SHOWS PANEL A, BUT THIS PANEL IS NOT |
| SHOWN ON THE PLAN. THERE IS A PANEL B SHOWN ON PLAN AND |
| THERE IS A PANEL SCHEDULE FOR PANEL B BUT IT IS NOT |
| SHOWN ON THE RISER DIAGRAM. SHOW LOCATION OF ALL |
| ELECTRICAL PANELS ON PLAN. ALSO, PROVIDE PANEL SCHEDULE |
| FOR PANEL A WITH A LOAD CALCULATION. PROVIDE CORRECTION |
| TO LOAD CALCULATION FOR PANEL B, ONE OF THE RTU'S IN |
| NOT INCLUDED SO THE MATH IS WRONG. WPB FBC 107.2.1; NEC |
| 215.5, 220, 408.4 |
| 2. PROVIDE AIC RATING OF NEW PANEL. NEC 110.3, 110.9 |
| 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| NEC 110.9, 110.10 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |