Plan Review Notes
Plan Review Notes For Permit 18041305
Permit Number 18041305
Review Stop E
Sequence Number 1
Notes
Date Text
2018-05-09 14:20:37CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. RISER DIAGRAM SHOWS PANEL A, BUT THIS PANEL IS NOT
 SHOWN ON THE PLAN. THERE IS A PANEL B SHOWN ON PLAN AND
 THERE IS A PANEL SCHEDULE FOR PANEL B BUT IT IS NOT
 SHOWN ON THE RISER DIAGRAM. SHOW LOCATION OF ALL
 ELECTRICAL PANELS ON PLAN. ALSO, PROVIDE PANEL SCHEDULE
 FOR PANEL A WITH A LOAD CALCULATION. PROVIDE CORRECTION
 TO LOAD CALCULATION FOR PANEL B, ONE OF THE RTU'S IN
 NOT INCLUDED SO THE MATH IS WRONG. WPB FBC 107.2.1; NEC
 215.5, 220, 408.4
 2. PROVIDE AIC RATING OF NEW PANEL. NEC 110.3, 110.9
 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  