Plan Review Notes
Plan Review Notes For Permit 18041299
Permit Number 18041299
Review Stop M
Sequence Number 2
Notes
Date Text
2018-05-29 11:46:082ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18041299
 5/29/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) WIND LOAD ENGINEERING IS REQUIRED FOR INSTALLATION
 OF THE NEW 5-TON RTU- SECTION 301.15. PLEASE PROVIDE
 THE DESIGN CRITERIA AND INSTALLATION DETAILS ON THE
 PLAN.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved