2018-05-09 17:14:431ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18041299
 5/9/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS C-1 & 4.0M: MECHANICAL NOTES #1 & #5 ON C-1
 SEEM TO INDICATE (3) 5-TON AC SYSTEMS WILL BE
 INSTALLED, HOWEVER THE PLAN SHOWS (2).
  
 2) REPLACEMENT OF THE AC SYSTEMS ARE NOT EXACT SAME
 SIZE REPLACEMENTS SO COOLING AND HEATING CALCULATIONS
 ARE REQUIRED TO VERIFY ACCURATE SIZING- SECTION
 C403.2.1 FBC-14 ENERGY CONSERVATION.
  
 3) 4.0M: PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION
 OF THE NEW ROOFTOP UNITS ON THE EXISTING CURBS. IF
 USING CURB ADAPTERS PLEASE INCLDUE THEM IN THE DETAILS
 AND SUBMIT SPECS- SECTION 301.15 FBC-17 MECHANICAL.
  
 4) SHEET C-1, NOTE 3 & SHEET 4.0M: SHOW THE LOCATIONS
 OF THE ROOFTOP HOODS AND PROVIDE CAPPING DETAILS.
  
 5) 4.0M: DUCT SMOKE DETECTORS ARE REQUIRED IN THE
 SUPPLY SYSTEMS OF THE NEW 5-TON RTU'S , UNLESS
 MANUFACTURER'S SPECIFICATIONS INDICATE THE SYSTEMS
 CANNOT PRODUCE OVER 2000 CFMS OF SUPPLY AIR- SECTION
 606.2.1.
  
 6) ONE SET OF PLANS IS MISSING THE 4.0M SHEET.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  