| 2ND REVIEW: |
| 2017 FLORIDA BUILDING CODE 6TH EDITION |
| 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| EDITION |
| |
| PLUMBING COMMENTS: PREVIOUS COMMENT NOT COMPLIED. |
| |
| 1) SHT. A2.02 - THE SINK IN THE PREASSEMBLY ROOM NEXT |
| TO ROOM #220 SHALL COMPLY WITH THE 2014 |
| FBC-ACCESSIBILITY SECS. 212.3, 606.2, 606.3, 606.4.THE |
| MAXIMUM HEIGHT OF THE COUNTERTOP/SINK SHALL BE A |
| MAXIMUM OF 34 INCHES ABOVE THE FINISH FLOOR PER THE |
| 2014 FBC-ACCESS. SEC. 606.3.//// THE RESPONSE LETTER |
| REFERS TO DETAIL # 1 ON SHT. ID. 5.13 I COULD NOT |
| LOCATE THAT SHEET IN THIS SUBMITTAL IT APPEARS TO BE |
| MISSING PLEASE INDICATE ON THE PLAN THE REQUIRED CLEAR |
| FLOOR SPACE AND THE SINK HEIGHT. |
| |
| 2) SHTS. A7.05 & A.7.41, DETAIL #14 - TOILET ROOM # 622 |
| - THE LAVATORY APPEARS TO BE ENCROACHING INTO THE 60 |
| INCH CLEAR FLOOR SPACE FOR THE WATER CLOSET. NO FIXTURE |
| MAY ENCROACH INTO THIS CLEAR FLOOR SPACE PER 2014 |
| FBC-ACCESS. SEC.604.3.2. //// THE RESPONSE TO THIS |
| COMMENT DOES NOT COMPLY WITH THE CODE DUE TO THE |
| OCCUPANT LOAD SEPARATE FACILITIES ARE REQUIRED AND BOTH |
| SHALL COMPLY WITH ACCESSIBILITY. PER FBC PL 403.2 AND |
| FBC ACC 213.1 |
| |
| 4) SUBMIT TWO COPIES OF COMPLETE MANUFACTURER'S |
| SPECIFICATIONS FOR THE AUTO-FUEL FILL MINI-SMART PUMP. |
| WPB AMEND. TO FBC SEC. 107.2.1.//// COMPLETE |
| SPECIFICATION AND INSTALLATION GUIDE IS REQUIRED THE |
| DETAIL ON THE PLAN IS JUST A GENERAL DRAWING AND DOES |
| NOT HAVE ANY DETAIL SUCH AS THE UL RATING OF THE MOTOR |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |
| GEORGE JOHNSON |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| 561-805-6711 |
| [email protected] |
| |
| |