Plan Review Notes For Permit 18041294
Permit Number 18041294
Review Stop P
Sequence Number 1
Notes
Date Text
2018-05-26 05:03:561) SHT. A2.02 - THE SINK IN THE PREASSEMBLY ROOM NEXT
 TO ROOM #220 SHALL COMPLY WITH THE 2014
 FBC-ACCESSIBILITY SECS. 212.3, 606.2, 606.3, 606.4.THE
 MAXIMUM HEIGHT OF THE COUNTERTOP/SINK SHALL BE A
 MAXIMUM OF 34 INCHES ABOVE THE FINISH FLOOR PERR THE
 2014 FBC-ACCESS. SEC. 606.3.
 2) SHTS. A7.05 & A.7.41, DETAIL #14 - TOILET ROOM # 622
 - THE LAVATORY APPEARS TO BE ENCROACHING INTO THE 60
 INCH CLEAR FLOOR SPACE FOR THE WATER CLOSET. NO FIXTURE
 MAY ENCROACH INTO THIS CLEAR FLOOR SPACE PER 2014
 FBC-ACCESS. SEC.604.3.2.
 3) THE SUBMITTED NARRATIVE LISTS SHT.P5.02 - THIS SHEET
 IS NOT INCLUDED IN THE SET OF PLANS.SUBMIT THIS SHEET
 FOR REVIEW AS IT CONTAINS THE CHANGES TO THE BOILER
 ROOM EQUIPMENT.
 4) SUBMIT TWO COPIES OF COMPLETE MANUFACTURER'S
 SPECIFICATIONS FOR THE AUTO-FUEL FILL MINI-SMART PUMP.
 WPB AMEND. TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
  
  