2018-05-14 11:00:131ST REVIEW FBC-2014 MECHANICAL
 REVISON PERMIT #18041294
 MASTER #16061443
 5/14/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS M2.08A, M4.01, M7.05: THERE IS A DISCREPANCY
 IN THE PLANS PETAINING TO HOW THE FLAMEBAR DUCTS ARE
 SHOWN TRANSITIONING FROM THE TE SHAFTS INTO THE
 INTERSTICIAL SPACE. SHEET M2.08 SHOWS HORIZONTAL
 TRANSITIONS, BUT SHEET M4.01 SHOWS VERTICAL
 TRANSITIONS. PLEASE NOTE NO DETAILS FOR VERTICAL
 TRANSITIONS ARE SHOWN ON M7.05.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  