2018-06-09 18:39:49 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| |
| 1. SEE FBC B 3306, IT APPEARS THAT A BARRIER AND |
| OVERHEAD PROTECTION ARE REQUIRED. ACQUIRE PERMITS OR |
| PROVIDE EVIDENCE THAT THE PERMITS HAVE ALREADY BEEN |
| OBTAINED. |
| |
| 2. REVISION 4 NARRATIVE STATES THAT A0.01, A1.01, AND |
| A1.01A WERE REVISED BUT THE SHEETS WERE NOT INCLUDED IN |
| THIS REVISION. |
| |
| 3. ISSUED SHEET A0.01 HAS A NOTE REGARDING THE 5% |
| FLORIDA SPECIAL ACCESSIBILITY ROOMS, BUT IT IS NOT |
| CLEAR WHICH ROOMS ARE DESIGNATED. REVISE PLAN AND CHART |
| ACCORDINGLY. SHOW THE GRAB BARS REQUIRED BY FBC A |
| 806.4(I) AND (III); NOTE WATER CLOSET REQUIREMENTS, |
| NOTE OPEN BED FRAME REQUIREMENT. |
| |
| 4. A1.12, IT IS NOT CLEAR HOW THE OCCUPANT LOAD WAS |
| REDUCED. MEETING ROOM 3 WITH 106 OCCUPANTS WAS |
| ELIMINATED AND THE AREA COMBINED WITH THE ADJACENT OPEN |
| AREA. IS THIS ALL NOW CONSIDERED "PRE-ASSEMBLY" WITH NO |
| OCCUPANTS? WE DID NOT REQUIRE OCCUPANTS TO BE COUNTED |
| IN THE PRE-ASSEMBLY AREAS AS THE OCCUPANT LOAD IN THE |
| MEETING ROOMS WAS CONSERVATIVE (7 SF PER PERSON, |
| ALTHOUGH TABLES AND CHAIRS ARE SHOWN). IT APPEARS THAT, |
| WITH THE ELIMINATION OF MEETING ROOM 3, PRE-ASSEMBLY |
| AREAS ARE LARGER THAN THE MEETING ROOMS. |
| |
| PLEASE ASSIGN AN AREA DESIGNATION (PRE-ASSEMBLY? OPEN |
| MEETING?) TO THIS AREA, AND ASSIGN AN OCCUPANT LOAD TO |
| THIS NEW LARGE OPEN AREA, OR CONTACT ME TO DISCUSS. |
| |
| 5. A1.12 AND A1.31 CONFLICT. ONE USES 7 SF/PERSON FOR |
| THE ASSEMBLY AREAS, THE OTHER USES 15 SF/PERSON AND |
| ALSO STATES THAT AREA OCCUPIED BY TABLES WAS DEDUCTED |
| FROM THE AREA. YOU CANNOT DEDUCT FURNITURE, REVISE |
| NOTES AND CORRELATE. IF 15 SF/PERSON IS USED TO |
| CALCULATE OCCUPANT LOAD, ALSO INCLUDE OCCUPANT LOAD IN |
| THE PRE-ASSEMBLY AREA AT 15 SF/PERSON OR EXPLAIN HOW |
| YOU CAN CONTROL THE NUMBER OF PEOPLE IN THIS AREA. |
| |
| 6. THE PURPOSE OF THE 18'10" DIMENSION IS NOT CLEAR. IT |
| APPEARS TO BE INDICATING REMOTENESS OF EXITS BUT IS NOT |
| MEASURING EXIT TO EXIT. |
| |
| 7. A1.16, ELECTRICAL ROOM, HOUSEKEEPING, TEXT IS NOT |
| CLEAR, PLEASE PRINT PROPERLY. |
| |
| 8. A1.16, A DOUBLE KING IS SHOWN; IS THIS ACCESSIBLE? |
| SINCE IT APPEARS TO BE THE ONLY DOUBLE KING IT APPEARS |
| THAT IT IS REQUIRED TO BE ACCESSIBLE. REVISE PLAN OR |
| CLARIFY. |
| |
| 9. A1.19, THE POOL GATES SHALL OPEN OUTWARD AWAY FROM |
| THE POOL AREA, FBC B 454.1.3.1.9. |
| |
| 10. A1.19, MENS ROOM DOOR 1322 APPEARS TO BE RECESSED |
| DUE TO THE COLUMN AND IT IS NOT CLEAR IF IT COMPLIES |
| WITH FBC A 404.2.4, 404.2.4.3. |
| |
| 11. A1.31, POSSIBLY OTHER PAGES, IT APPEARS THAT NOT |
| ALL CHANGES WERE CLOUDED. FOR INSTANCE, THE POOL GATES |
| ARE NOT CLOUDED. THE OVERALL PLANS ARE DIFFICULT TO |
| READ DUE TO THE AMOUNT OF GRAPHICS; CLOUDED CHANGES ARE |
| NEEDED ON THE OTHER PAGES TO EXPEDITE PLAN REVIEW, FBC |
| 107. |
| |
| 12. A2.06, FBC A 1004.1, REVISE TO SHOW COMPLIANCE FOR |
| EXERCISE EQUIPMENT. |
| |
| 13. A3.09, A7.22A, POSSIBLY OTHER LOCATIONS, FBC B 603, |
| A WOOD CEILING IS SHOWN. THIS DOES NOT APPEAR TO BE |
| PERMITTED. REVISE OR CONTACT ME TO DISCUSS. |
| |
| 14. A7.01, A7.02, POSSIBLY OTHER PAGES; PLYWOOD IS |
| PROPOSED; WILL THIS BE FRT? IF YES, REVISE PER FBC B |
| 603. IF NOT, NOTE SF AREA; A MINIMAL AMOUNT IS ALLOWED |
| AS BACKING. NOTE SF AREA AND EXCEPTION IF FRT IS NOT |
| PROPOSED. |
| |
| |