2018-06-15 13:08:04 | ****CORRECTIONS**** |
| COURTESY REVIEW TO FURTHER CLARIFY PLAN REVIEW ISSUES |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| FBC R = FBC RESIDENTIAL |
| |
| 1. FBC B CHAPTER 10, FBC ACCESSIBILITY, MEANS OF EGRESS |
| NOT CLEAR. REVISE PLAN TO SHOW COMPLIANCE WITH, OR |
| CLARIFY; 1-A1.101, CONSTRUCTION PLAN - PLAZA, DOES NOT |
| SHOW ALL EXIT DOORS AND THE ACCESSIBLE ROUTE. THERE ARE |
| PARALLEL LINES AT THE EAST LOBBY EXIT DOOR; ARE THESE |
| STAIRS? IF NOT STAIRS, WHAT DO THE LINES DEPICT? THERE |
| IS A "TENANT SPACE" AREA TO THE WEST OF THE PLAZA, |
| APPEARS TO INCLUDE SIX EXIT DOORS, BUT THE DOORS ARE |
| EXCLUDED FROM THE "ACCESSIBLE ROUTE". FBC 107. |
| |
| 2. A-1.01, NOTE 22 IS "NEW STEPS, SEE LANDSCAPE". NOTE |
| 17 IS "NEW ACCESSIBLE CONCRETE RAMP". PLEASE REVISE |
| PLAN TO INCLUDE THE FOLLOWING: |
| |
| 1-LS2.03 HAS DETAILS FOR RAMP AND STAIR. THERE IS A |
| NOTE POINTING TO THE STAIR, "REINFORCING, REF |
| STRUCTURAL"; ANOTHER NOTE WHICH STATES "COMPACTED SUB |
| GRADE PER GEOTECH OR CIVIL RECOMMENDATION". WHERE ON |
| THE CIVILS? PLEASE PROVIDE SOILS REPORT IF IT'S DESIGN |
| TEAM'S INTENT THAT A SOILS REPORT SPECIFIES SOIL |
| COMPACTION. |
| |
| ADVISE WHERE THE STRUCTURAL DETAIL FOR THE RAMP CAN BE |
| LOCATED ON STRUCTURAL PLAN, OR REVISE PLAN TO INCLUDE. |
| |
| 3. REVISE PLAN TO CLEARLY SHOW THE RISE AND WIDTH OF |
| RAMPS AND STAIRS. IT IS NOT CLEAR IF TWO OR MORE |
| HANDRAILS ARE REQUIRED. HANDRAIL IS SHOWN ON THE DETAIL |
| BUT NOT ON THE PLAN. |
| |
| 4. REVISE PLAN TO PROVIDE A PLAN FOR THE RAMP WHICH |
| SHOWS LANDINGS, TURNS IF APPLICABLE, RUN DIMENSION. |
| |
| 5. RAMPS AND STAIRS ARE NOT SHOWN ON S1.101 "STRUCTURAL |
| AREA OF WORK PLAN". IT APPEARS THAT A STRUCTURAL DETAIL |
| FOR RAMP IS REQUIRED. |
| |
| SEE FBC A 405, 504, 505, FBC B CHAPTER 10, FBC 107 |
| |
| |