2018-04-27 16:40:33 | BUILDING PLAN REVIEW |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER, PX3169 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 1ST REVIEW |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. E-84 TEST REPORT FOR SURFACE BURNING CHARACTERISTICS |
| OF BUILDING MATERIALS FOR THE SPECIMEN SHAW SUNDRIES |
| GROUND WORKS STYLE 074VS IS NOT VALID WITHOUT |
| ENGINEER'S SEAL. |
| 2. PROVIDE CERTIFIED TEST REPORTS FOR ASTM E-90, |
| AIRBORNE SOUND AND ASTM E-492, IMPACT SOUND FOR |
| PROPOSED UNDERLAYMENT. |
| |
| PROVIDE THE FOLLOWING INFORMATION FOR FLOORING |
| SUBMITTALS: |
| |
| 1. FLOOR PLAN WITH DIMENSIONS AND LOCATION OF WORK. - |
| COMPLIED |
| *DESIGNER TO PRINT NAME AND SIGN PLAN PER FBC 107 * |
| 2. TOTAL SQUARE FOOTAGE OF NEW FLOORING. - COMPLIED |
| 3. TYPE OF PROPOSED FLOORING |
| (TILE/MARBLE/LAMINATE/WOOD/OTHER). - VINYL PLANK |
| 4. STATED VALUE OF WORK. - VALUE SHALL BE BASED ON |
| LABOR AND MATERIALS |
| 5. EXISTING SITE CONDITIONS: |
| A) THICKNESS OF SLAB. B) CEILING ASSEMBLY (OPEN |
| CONCRETE/SUSPENDED GYPSUM/ACOUSTICAL) |
| 6. PROPOSED UNDERLAYMENT. - STATED |
| 7. TEST REPORTS FOR PROPOSED UNDERLAYMENT BASED ON |
| EXISTING SITE CONDITIONS. |
| 8. TEST REPORTS MAY BE BASED ON THE FOLLOWING ASTM?S, |
| E-84, E-90 & E-492. |
| 9. ALL DOCUMENTS SHALL BE SUBMITTED IN DUPLICATE. |
| |
| FBC 603.1 FLAME SPREAD ? ASTM E-84-09 |
| |
| FBC 1207.2 AIR-BORNE SOUND. ASTM E ? 90-04 |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E 90. |
| |
| FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E ? 492-09 |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC SPACE OR SERVICE |
| AREA WITHIN THE STRUCTURE SHALL HAVE AN IMPACT |
| INSULATION CLASS (IIC) RATING OF NOT LESS THAN 50 (45 |
| IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E |
| 492. |
| |
| |