Plan Review Notes For Permit 18041163
Permit Number 18041163
Review Stop G
Sequence Number 1
Notes
Date Text
2018-06-04 03:59:431) SHOW THE DISTANCE FROM THE OUTLET OF THE GAS METER
 TO THE INLET OF THE MP REGULATOR FOR THE EXISTING
 INTERIOR LOAD ON THAT SECTION.2017 FBC-FUEL GAS SEC.
 402.4.1.
 2) LIST THE EXISTING GAS FIXTURES ON THE PLAN AND THE
 CORRESPONDING BTU LOAD FOR EACH APPLIANCE. WPB AMEND.
 TO FBC SEC. 107.2.1.
 3) SHOW THE DISTANCE FROM THE OUTLET OF THE MP
 REGULATOR TO THE MOST REMOTE OUTLET ON THE INTERIOR
 SECTION OF THE SYSTEM.2017 FBC-FUEL GAS SEC.402.4.1.
 THE EXISTING GAS PLANS ON FILE AT THE CITY SHOW THE
 MOST REMMOTE OUTLET AT 83 FEET FROM THE METER. CLARIFY.
 4) THE SHUTOFF VALVE ON THE EXISTING PIPING TO THE
 INTERIOR SHALL BE LOCATED IMMEDIATELY AHEAD OF THE
 REGULATOR PER 2017 FBC-FUEL GAS SEC. 409.4.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
  
  
  