Plan Review Notes
Plan Review Notes For Permit 18041159
Permit Number 18041159
Review Stop G
Sequence Number 2
Notes
Date Text
2018-07-30 06:26:301) SHOW THE TYPE OF PIPE AND THE PIPE SIZE AT THE
 OUTLET OF THE 2 PSI METER. WPB AMEND. TO FBC SEC.
 107.2.1. THE EXISTING PLANS ON FILE WITH THE CITY SHOW
 AN EXISTING 1 1/2 INCH LINE. WILL THIS REMAIN OR BE
 CHANGED? CLARIFY.2ND REQUEST.
 2) THE SUBMITTED GAS DRAWING SHOWS THE PIPE SIZE OF THE
 SECTION OF PIPE TO THE REGULATOR SERVING THE EXISTING
 GAS LOAD AS 3/4 INCH.. THE PLANS ON FILE WITH THE CITY
 SHOWS AN 1 1/4 INCH LINE TO THE INTERIOR. WILL THIS
 LINE BE REPLACED WITH A 3/4 INCH LINE? CLARIFY. 2ND
 REQUEST.
 3) THE GAS PLAN ON FILE AT THE CITY SHOWS A 1 INCH GAS
 LINE TO THE POOL HEATER AND THE SUBMITTED GAS DRAWING
 SHOWS A 3/4 INCH LINE. CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  