2018-07-30 06:26:30 | 1) SHOW THE TYPE OF PIPE AND THE PIPE SIZE AT THE | | OUTLET OF THE 2 PSI METER. WPB AMEND. TO FBC SEC. | | 107.2.1. THE EXISTING PLANS ON FILE WITH THE CITY SHOW | | AN EXISTING 1 1/2 INCH LINE. WILL THIS REMAIN OR BE | | CHANGED? CLARIFY.2ND REQUEST. | | 2) THE SUBMITTED GAS DRAWING SHOWS THE PIPE SIZE OF THE | | SECTION OF PIPE TO THE REGULATOR SERVING THE EXISTING | | GAS LOAD AS 3/4 INCH.. THE PLANS ON FILE WITH THE CITY | | SHOWS AN 1 1/4 INCH LINE TO THE INTERIOR. WILL THIS | | LINE BE REPLACED WITH A 3/4 INCH LINE? CLARIFY. 2ND | | REQUEST. | | 3) THE GAS PLAN ON FILE AT THE CITY SHOWS A 1 INCH GAS | | LINE TO THE POOL HEATER AND THE SUBMITTED GAS DRAWING | | SHOWS A 3/4 INCH LINE. CLARIFY. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | | | | | |
|