2018-05-17 11:26:24 
 1) SHOW THE TYPE OF PIPE AND PIPE SIZE AT THE OUTLET OF
 THE 2 PSI METER . WPB AMEND. TO FBC SEC. 107.2.1.
 2) SHOW THE PIPE SIZE OF THE SECTION OF PIPE TO THE
 REGULATOR SERVING THE EXISTING GAS LOAD.WPB AMEND. TO
 FBC SEC. 107.2.1.
 3) SHOW THE TYPE OF PIPE AND PIPE SIZE DOWNSTREAM OF
 THE REGULATOR FOR THE EXISTING GAS LOADS AND NOTE THE
 DISTANCE FROM THIS REGULATOR TO THE FURTHEST OUTLET ON
 THAT SYSTEM.WPB AMEND. TO FBC SEC. 107.2.1.
 4) A LISTED SHUTOFF VALVE IS REQUIRED IMMEDIATELY AHEAD
 OF THE MP REGULATOR FOR THE EXISTING LOADS.. 2017 FBCR
 SEC. G2420.4.
 5) SPECIFY ON THE GAS DRAWING HOW THE 3/4 INCH
 GALVANIZED PIPE IS GOING TO BE INSTALLED. ABOVE-GROUND
 PIPING OUTDOORS SHALL COMPLY WITH 2017 FBCR
 SEC.G2415.9, G2415.11.
 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FLEX
 CONNECTOR FOR THE GENERATOR. THE FLEX CONNECTOR SHALL
 BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE
 GENERATOR. 2017 FBCR SEC. G2422.1 (8).
 7) THE SEDIMENT TRAP AS DRAWN DOES NOT COMPLY WITH 2017
 FBCR SEC.G2419.4.
 8) SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION SHEETS FOR THE REGULATORS. REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE
 APPROVED FOR OUTDOOR INSTALLATION. 2017 FBCR
 SEC.G2421.1, FBC-FUEL GAS SEC. 410.1.
 9) LIST THE EXISTING GAS FIXTURES ON THE PLAN AND THE
 CORRESPONDING BTU LOAD FOR EACH APPLIANCE. WPB AMEND.
 TO FBC SEC .107.2.1, 2017 FBC-FUEL GAS SEC.402.1.
 10) CITY RECORDS SHOW THE BTU LOAD OF THE EXISTING
 SYSTEM AS 585, 000 BTU'S AND THE SUBMITTED PLAN SSHOWS
 525,000. REVISE THE EXISTING BTU LOAD.
  
  