Date |
Text |
2018-06-29 07:46:08 | 1) THE EXISTING GAS PLANS ON FILE AT THE CITY SHOW A |
| SUMMER KITCHEN WITH A 55,000 BTU LOAD BUT THIS IS NOT |
| SHOWN ON THE SUBMITTED GAS DRAWING. REVISE THE GAS |
| DRAWING TO REFLECT THE SUMMER KITCHEN AND REVISE THE |
| TOTAL BTU LOAD ON THE GAS DOCUMENTS. WPB AMEND. TO FBC |
| SEC. 107.2.1, 2017 FBC-FUEL GAS SEC.401.3, 401.4. |
| 2) THE SHUTOFF VALVE ON THE 3/4 INCH EXISTING LINE INTO |
| THE STRUCTURE SHALL BE LOCATED IMMEDIATELY AHEAD OF THE |
| REGULATOR. 2017 FBC-FUEL GAS SEC.409.4. |
| 3) SHOW THE DISTANCE FROM THE MP REGULATOR FOR THE |
| EXISTING LINE INTO THE STRUCTURE TO THE MOST REMOTE GAS |
| OUTLET ON THAT SECTION. THIS DISTANCE WILL DETERMINE |
| THE PIPE SIZING.THE EXISTING PLANS ON FILE SHOW THE |
| LONGEST RUN AS 100 FEET. |
| 4) THE EXISTING PLANS ON FILE AT THE CITY SHOW THE PIPE |
| SIZE AT THE METER OUTLET AS 1 INCH AND THE SUBMITTED |
| PLAN SHOWS 3/4 INCH. CLARIFY. |
| 5) SHOW THE PIPE SIZE OF THE PE ON THE GAS PLAN. WPB |
| AMEND. TO FBC SEC. 107.2.1. |
| 6) SHOW THE DISTANCE FROM THE METER TO THE REGULATOR |
| FOR THE EXISTING LINE INTO THE STRUCTURE. |
| |
| NOTE: THE SAME GAS DRAWING THAT WAS REJECTED ON THE |
| REVIEW OF 6/3 HAS BEEN RESUBMITTED AND REJECTED AGAIN |
| BECAUSE NONE OF THE CORRECTIONS WERE MADE. RESUBMITTAL |
| OF THESE PLANS WILL REQUIRE PAYMENT OF 4X THE PLAN |
| REVIEW FEE IN ACCORDANCE WITH FL. STATUTE 553.80 (2) |
| (B). |
| |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| PLUMBING PLAN REVIEW |
| 561-805-6692 |
| |