Plan Review Notes
Plan Review Notes For Permit 18041158
Permit Number 18041158
Review Stop G
Sequence Number 2
Notes
Date Text
2018-06-03 13:55:331) THE EXISTING GAS PLANS ON FILE AT THE CITY SHOW A
 SUMMER KITCHEN WITH A 55,000 BTU LOAD BUT THIS IS NOT
 SHOWN ON THE SUBMITTED GAS DRAWING. REVISE THE GAS
 DRAWING TO REFLECT THE SUMMER KITCHEN AND REVISE THE
 TOTAL BTU LOAD ON THE GAS DOCUMENTS. WPB AMEND. TO FBC
 SEC. 107.2.1, 2017 FBC-FUEL GAS SEC.401.3, 401.4.
 2) THE SHUTOFF VALVE ON THE 3/4 INCH EXISTING LINE INTO
 THE STRUCTURE SHALL BE LOCATED IMMEDIATELY AHEAD OF THE
 REGULATOR. 2017 FBC-FUEL GAS SEC.409.4.
 3) SHOW THE DISTANCE FROM THE MP REGULATOR FOR THE
 EXISTING LINE INTO THE STRUCTURE TO THE MOST REMOTE GAS
 OUTLET ON THAT SECTION. THIS DISTANCE WILL DETERMINE
 THE PIPE SIZING.THE EXISTING PLANS ON FILE SHOW THE
 LONGEST RUN AS 100 FEET.
 4) THE EXISTING PLANS ON FILE AT THE CITY SHOW THE PIPE
 SIZE AT THE METER OUTLET AS 1 INCH AND THE SUBMITTED
 PLAN SHOWS 3/4 INCH. CLARIFY.
 5) SHOW THE PIPE SIZE OF THE PE ON THE GAS PLAN. WPB
 AMEND. TO FBC SEC. 107.2.1.
 6) SHOW THE DISTANCE FROM THE METER TO THE REGULATOR
 FOR THE EXISTING LINE INTO THE STRUCTURE.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
  