Plan Review Notes
Plan Review Notes For Permit 18041158
Permit Number 18041158
Review Stop G
Sequence Number 1
Notes
Date Text
2018-05-15 05:26:00 
 1) SHOW THE TYPE OF PIPE AND PIPE SIZE AT THE OUTLET OF
 THE 2 PSI METER . WPB AMEND. TO FBC SEC. 107.2.1.
 2) SHOW THE PIPE SIZE OF THE SECTION OF PIPE TO THE
 REGULATOR SERVING THE EXISTING GAS LOAD.WPB AMEND. TO
 FBC SEC. 107.2.1.
 3) SHOW THE TYPE OF PIPE AND PIPE SIZE DOWNSTREAM OF
 THE REGULATOR FOR THE EXISTING GAS LOADS AND NOTE THE
 DISTANCE FROM THIS REGULATOR TO THE FURTHEST OUTLET ON
 THAT SYSTEM.WPB AMEND. TO FBC SEC. 107.2.1.
 4) A LISTED SHUTOFF VALVE IS REQUIRED IMMEDIATELY AHEAD
 OF THE MP REGULATOR FFOR THE EXISTING LOADS.. 2017 FBCR
 SEC. G2420.4.
 5) SPECIFY ON THE GAS DRAWING HOW THE 3/4 INCH
 GALVANIZED PIPE IS GOING TO BE INSTALLED. ABOVE-GROUND
 PIPING OUTDOORS SHALL COMPLY WITH 2017 FBCR
 SEC.G2415.9, G2415.11.
 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FLEX
 CONNECTOR FOR THE GENERATOR. THE FLEX CONNECTOR SHALL
 BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE
 GENERATOR. 2017 FBCR SEC. G2422.1 (8).
 7) THE SEDIMENT TRAP AS DRAWN DOES NOT COMPLY WITH 2017
 FBCR SEC.G2419.4.
 8) LIST THE EXISTING GAS FIXTURES ON THE PLAN AND THE
 CORRESPONDING BTU LOAD FOR EACH APPLIANCE. WPB AMEND.
 TO FBC SEC .107.2.1, 2017 FBC-FUEL GAS SEC.402.1.
 9) SUBMIT CLEAR AND LEGIBLE SPECIFICATIONS FOR THE
 GENERATOR. SOME AREAS ON THE SHEETS CANNOT BE READ. WPB
 AMEND. TO FBC SEC. 1107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  