Plan Review Notes
Plan Review Notes For Permit 18041146
Permit Number 18041146
Review Stop P
Sequence Number 2
Notes
Date Text
2018-10-01 14:54:521) THE AFFIDAVIT OF COMPLIANCE FOR THE POOL BARRIER
 REFERS TO THE 2017 FBC WITH 2006 SUPPLEMENTS EFFECTIVE
 DECEMBER 8, 2006. IF THE DATES ARE TO BE ERASED WITH
 WITE OUT AND REDONE IT WOULD PROBABLY BE BEST TO MAKE
 SURE ALL THE DATES ARE THE SAME. AS AN FYI, THERE ARE
 NO SUPPLEMENTS TO THE 2017 FBC AND THE 2017 FBC TOOK
 EFFECT ON DECEMBER 31ST, 2017, NOT DECEMBER 8,2006. IN
 ADDITION, THIS DOCUMENT IS A NOTARIZED DOCUMENT AND IS
 NOT TO BE CHANGED. SUBMIT A NEW ORIGINAL CCORRECTED
 DOCUMENT THAT REFERENCES THE CORRECT BUILDING CODE AND
 CODE SECTIONS. REFER TO COMMENT #1 FROM MY FIRST
 REVIEW.
 2) AN AMENDED OPERATING PERMIT APPROVAL IS REQUIRED
 FROM THE PALM BEACH COUNTY HEALTH DEPT. BECAUSE OF THE
 RELOCATION OF THE MAIN DRAIN, CHAIR- LIFT, LADDDER,
 ETC. A COPY OF FORM DH 4159 APPROVED BY THE PBC HEALTH
 DEPT. FOR THE MODIFICATION MUST BE SUBMITTED FOR
 REVIEW.
 3) THE GAS DRAWING CANNOT BE SUBMITTED FOR REVIEW UNDER
 THIS POOL PERMIT. A SEPARATE REVISION MUST BE SUBMITTED
 FOR REVIEW UNDER THE EXISTING GAS PERMIT NUMBER.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  