2018-10-01 14:54:52 | 1) THE AFFIDAVIT OF COMPLIANCE FOR THE POOL BARRIER | | REFERS TO THE 2017 FBC WITH 2006 SUPPLEMENTS EFFECTIVE | | DECEMBER 8, 2006. IF THE DATES ARE TO BE ERASED WITH | | WITE OUT AND REDONE IT WOULD PROBABLY BE BEST TO MAKE | | SURE ALL THE DATES ARE THE SAME. AS AN FYI, THERE ARE | | NO SUPPLEMENTS TO THE 2017 FBC AND THE 2017 FBC TOOK | | EFFECT ON DECEMBER 31ST, 2017, NOT DECEMBER 8,2006. IN | | ADDITION, THIS DOCUMENT IS A NOTARIZED DOCUMENT AND IS | | NOT TO BE CHANGED. SUBMIT A NEW ORIGINAL CCORRECTED | | DOCUMENT THAT REFERENCES THE CORRECT BUILDING CODE AND | | CODE SECTIONS. REFER TO COMMENT #1 FROM MY FIRST | | REVIEW. | | 2) AN AMENDED OPERATING PERMIT APPROVAL IS REQUIRED | | FROM THE PALM BEACH COUNTY HEALTH DEPT. BECAUSE OF THE | | RELOCATION OF THE MAIN DRAIN, CHAIR- LIFT, LADDDER, | | ETC. A COPY OF FORM DH 4159 APPROVED BY THE PBC HEALTH | | DEPT. FOR THE MODIFICATION MUST BE SUBMITTED FOR | | REVIEW. | | 3) THE GAS DRAWING CANNOT BE SUBMITTED FOR REVIEW UNDER | | THIS POOL PERMIT. A SEPARATE REVISION MUST BE SUBMITTED | | FOR REVIEW UNDER THE EXISTING GAS PERMIT NUMBER. | | | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | |
|