2018-05-13 09:37:461) THE AFFIDAVIT OF COMPLIANCE FOR THE POOL BARRIER
 REFERS TO THE 2004 FBC. THE CODE IN EFFECT IS THE 2017
 FBC. SUBMIT A NEW CERTIFICATE OF COMPLIANCE REFERENCING
 THE CORRECT CODE EDITION AND CODE SECTION. SEC. 454 IN
 THE 2017 FBC APPLIES TO SWIMMING POOLS.
 2) SHT. 3 OF 5 - SHOW THE DISTANCE OF THE FLOOR OUTLETS
 FROM THE WALL ADJACENT TO THE MAIN DRAIN. 2017 FBC SEC.
 454.1.6.5.9.2.
 3) SUBMIT MANUF. SPECIFICATIONS FOR THE MAIN DRAIN
 GRATE. WPB AMEND. TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  