Plan Review Notes For Permit 18041055 |
Permit Number |
18041055 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-04-26 07:18:27 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | 1. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND VALUE | | OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. | | FBC 109.3 (DESIGNER OF PLAN MUST PRINT AND SIGN). | | | | 2.PLAN IS REQUIRED TO BE SIGNED AND SEALED BY A DESIGN | | PROFESSIONAL OR THE ELECTRICAL CONTRACTOR | | QUALIFIER. FS 471.003(2)(H); 471.025; FBC 107.2.1 | | | | END OF COMMENTS. | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN | | REVIEW COMMENTS. WHEN RESUBMITTING, IT IS HELPFUL TO | | PROVIDE A RESPONSE LETTER ADDRESSING | | EACH ITEM ALONG WITH THE CITY RESUBMITTAL FORM. | | ADDITIONALLY, INSERT CORRECTED PAGES INTO | | THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | | | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 6TH EDITION | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 6TH | | EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 6TH EDITION, PART | | VIII ELECTRICAL | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | FRANK GIAQUINTO | | ELECTRICAL INSPECTOR | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES | | [email protected] | | 561-657-1653 |
|