Plan Review Notes
Plan Review Notes For Permit 18041047
Permit Number 18041047
Review Stop P
Sequence Number 1
Notes
Date Text
2018-06-06 10:29:161) SHOW THE FIXTURE CLEARANCES OF THE PLUMBING FIXTURES
 ON THE FLOOR PLANS. COMPLY WITH 2017 FBCR SEC.P2705.
 2) SHT.A-4.2.0.2 - DETAIL #8 - THE SHOWER SHALL BE
 PITCHED 1/4 OF AN INCH PER FOOT TO THE DRAIN (2%
 SLOPE).
 3) SHT. L-1 - SPRINKLER HEADS SHALL BE LOCATED A
 MINIMUM OF 1 FOOT FROM THE STRUCTURE SIDEWALL PER 2017
 FBCR SEC. R318.
 4) SHT. P.0.0.00B - PLUMBING SPECIFICATIONS 2.00 -
 BASIC METHODS AND MATERIALS - NOTE # 2.1 REFERS TO THE
 2014 FPC.THE CODE IN EFFECT FOR THIS PROJECT IS THE
 2017 FPC. REVISE THE NOTE.
 5) SHT. P.13.00B - SANITARY KEYED NOTE #2 - THE T & P
 VALVE DISCHARGE SHALL COMPLY WITH 2017 FBCR
 SEC.P2804.6.1.
 6) SHT. P1.4.00B - GENERAL DOMESTIC WATER NOTE #1
 REFERS TO FPC SEC.103.3(2). THERE IS NO SUCH SECTION.
 CLARIFY.
 7) P.1.3.01B - THE WASHING MACHINE ON THE SECOND FLOOR
 IS NOT PERMITTED ON A WET VENT PER 2017 FBCR
 SEC.P3108.1 ONLY FIXTURES IN THE BATHROOM GROUP ARE
 PERMITTED TO DISCHARGE INTO A WET VENT.
 8) P.1.3.00B - THE 2ND FLOOR MASTER BATH IS DISCHARGING
 6 FIXTURE UNITS INTO A 2 INCH WET VENT. A MAXIMUM OF 4
 FIXTURE UNITS SHALL DISCHARGE INTO A 2 INCH WET VENT
 PER 2017 FBCR TABLE P3108.3.
 9) A BACKFLOW DEVICE WILL BE REQUIRED ON THE WATER
 SERVICE.
 10) SHT. P.4.0.00B - SHOW THE SIZE OF THE EXPANSION
 TANK ON DETAIL #1.
 11) THE MINIMUM EF RATING FOR THE WATER HEATER SHALL BE
 .95 PER 2017 FBC-ENERGY SEC.R403.5.6.2.
 12) THE EXPANSION TANK IS NOT SHOWN ON THE WATER RISER.
 13) IF THE GAS GRILL IS INSTALLED AT THE SUMMER
 KITCHEN, THEN A HOOD WILL BE REQUIRED OVER THE GRILL.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
  