Date |
Text |
2018-06-11 12:12:42 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2017 6TH ED. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC |
| 210.8(D); FBC RE E3902.10 |
| 2. GFCI RECEPTACLES IN GARAGE ARE SHOWING AS OPTIONAL. |
| A MINIMUM OF ONE RECEPTACLE OUTLET PER CAR SPACE IS |
| REQUIRED. PROVIDE CORRECTION. NEC 210.52 (G)(1); FBC RE |
| E3901.9 |
| 3. CIRCUIT A-34 FOR CENTRAL VAC IS SHOWN WITH A |
| STANDARD RECEPTACLE. GFCI PROTECTION IS REQUIRED FOR |
| ALL OUTLETS IN GARAGE. PROVIDE CORRECTION. NEC 210.8; |
| FBC RE E3902.2 |
| 4. CIRCUIT A-19 IS SHOWN AS A GARAGE RECEPTACLE AND A |
| FRONT PORCH RECEPTACLE. THE BRANCH CIRCUIT SUPPLYING |
| RECEPTACLES IN A GARAGE SHALL NOT SUPPLY OUTLETS |
| OUTSIDE OF THE GARAGE. PROVIDE CORRECTION. NEC 210.52 |
| (G)(1); FBC RE E3901.9 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |
| SINCERELY, |
| |
| JOHN PEARSON |
| ELECTRICAL PLANS EXAMINER |
| 561-805-6746 |
| [email protected] |
| |