Plan Review Notes
Plan Review Notes For Permit 18041046
Permit Number 18041046
Review Stop B
Sequence Number 1
Notes
Date Text
2018-06-29 09:24:13BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE SOILS REPORT.
 FBC 1803.1 GENERAL.GEOTECHNICAL INVESTIGATIONS SHALL BE
 CONDUCTED IN ACCORDANCE WITH SECTION 1803.2 AND
 REPORTED IN ACCORDANCE WITH SECTION 1803.6. WHERE
 REQUIRED BY THE BUILDING OFFICIAL OR WHERE GEOTECHNICAL
 INVESTIGATIONS INVOLVE IN-SITU TESTING, LABORATORY
 TESTING OR ENGINEERING CALCULATIONS, SUCH
 INVESTIGATIONS SHALL BE CONDUCTED BY A REGISTERED
 DESIGN PROFESSIONAL.
  
 2. PROVIDE ENERGY SUBMITTAL. PROVIDE DETAIL FOR ROOF
 AND WALL INSULATION.
 FBCE-103.2.1.1 RESIDENTIAL LESS THAN OR EQUAL TO 3
 STORIES. ENERGY
  
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
 _ OR _
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 3. VALUE HAS BEEN ADJUSTED FROM $130,410 TO $255,136
 BASED ON THE LATEST PUBLISHED DATA FROM THE
 INTERNATIONAL CODE COUNCIL BUILDING VALUATION DATA.
  
 4. PROVIDE SITE PLAN WITH DRAINAGE PLAN.
 FBC 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS
 SUBMITTED WITH THE APPLICATION FOR PERMIT SHALL BE
 ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE THE SIZE
 AND LOCATION OF NEW CONSTRUCTION AND EXISTING
 STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE
 ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED
 GRADES AND, AS APPLICABLE, FLOOD HAZARD AREAS,
 FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT SHALL BE
 DRAWN IN ACCORDANCE WITH AN ACCURATE BOUNDARY LINE
 SURVEY.
 FBC R401.3 SITE DRAINAGE
 PROVIDE TWO SETS OF A SITE DRAINAGE PLAN SHOWING
 COMPLIANCE WITH FBC R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD.
 LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES WITHIN THE FIRST 10 FEET.
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES OF FALL WITHIN 10
 FEET, DRAINS OR SWALES SHALL BE CONSTRUCTED TO ENSURE
 DRAINAGE AWAY FROM THE STRUCTURE.
 IMPERVIOUS SURFACES WITHIN 10 FEET OF THE BUILDING
 FOUNDATION SHALL BE SLOPED A MINIMUM OF
 2 PERCENT AWAY FROM THE BUILDING.
  
 5. PALM BEACH COUNTY IMPACT FEES REQUIRED.
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.
  
 6. UP DATE BUILDING CODE DATA AND APPLICABLE CODES ON
 THE PLANS TO THE 2017 FBC SIXTH EDITION. THE PLANS HAVE
 SEVERAL REFERENCES TO THE FBC FIFTH EDITION (2014). THE
 FBC SIXTH EDITION (2017) WENT INTO EFFECT ON JANUARY 1,
 2018. ALL NEW PERMITS APPLIED FOR ON OR AFTER THAT DATE
 ARE REQUIRED TO COMPLY WITH AND REFERENCE THE FBC SIXTH
 EDITION (2017). FS CHAPTER 553.
  
 7. UP DATE THE BUILDING ELEVATION DATA ON SHEET
 A-0.0.01A TO REFLECT THE CURRENTLY ADOPTED FLOOD MAPS
 AND DATUM. AS OF OCTOBER 5TH, 2017 THE CITY HAS ADOPTED
 NEW FLOOD INSURANCE RATE MAPS WHICH USE NAVD 88 AS THE
 VERTICAL DATUM. THE CITY ALSO ADOPTED A 2' FREEBOARD
 WHICH REQUIRES THE FINISH FLOOR AND EQUIPMENT TO BE A
 MINIMUM OF TWO FEET ABOVE THE BFE.
  
 8. THE FIRE RESISTANCE RATING REQUIREMENTS ON SHEET
 A-0.0.01A IS MISLEADING WITHOUT THE REQUIRED MINIMUM
 FIRE SEPARATION BEING PROVIDED. SEE FBCR TABLE R302.1.
  
 9. FBC- R310.2.1 IS THE CODE SECTION FOR EMERGENCY
 ESCAPE AND RESCUE IN THE 2017 FBC SIXTH EDITION. THE
 CODE SECTION PROVIDED ON THE PLANS IS INCORRECT. FBC
 107.2.1
  
 10. THE NOTE UNDER EXTERIOR OPENINGS ON SHEET A-0.0.01A
 IS NOT WORDED CORRECTLY. FBC R311.3.2 STATES THAT THE
 LANDINGS AT EXTERIOR DOORS SHALL NOT BE MORE THAN 7-3/4
 INCHES BELOW THE TOP OF THE THRESHOLD.
  
 11. THE 2014 EDITION IS REFERENCED ON THE ATTIC
 VENTILATION ANALYSIS ON SHEET A-1.4.01A. PLEASE UPDATE
 TO THE 2017 FBC.
  
 12. PROVIDE STRUCTURAL DETAILS FOR THE TRUSS TO WALL
 CONNECTIONS FOR THE OPTIONAL CUPOLA THAT IS SHOWN ON
 SHEETS S-2.01B,C AND S-3.00B,C. THE NOTE ON SHEET
 S-2.01B,C FOR THE CUPOLA STATES THAT THE TOWER
 STRUCTURE IS BY TRUSS SPECIALTY ENGINEER. IT APPEARS
 THAT THE WALLS FOR THE CUPOLA ARE TO BE HAND FRAMED ON
 SITE PER DETAIL S-3.00B,C. CLARIFY.FBC 107.2.1
  
 13. SHOW COMPLIANCE WITH FBC-R318.1 R318.1 TERMITE
 PROTECTION. TERMITE PROTECTION SHALL BE PROVIDED BY
 REGISTERED TERMITICIDES, INCLUDING SOIL APPLIED
 PESTICIDES, BAITING SYSTEMS, AND PESTICIDES APPLIED TO
 WOOD, OR OTHER APPROVED METHODS OF TERMITE PROTECTION
 LABELED FOR USE AS A PREVENTATIVE TREATMENT TO NEW
 CONSTRUCTION. SEE SECTION 202, REGISTERED TERMITICIDE.
 UPON COMPLETION OF THE APPLICATION OF THE TERMITE
 PROTECTIVE TREATMENT, A CERTIFICATE OF COMPLIANCE SHALL
 BE ISSUED TO THE BUILDING DEPARTMENT BY THE LICENSED
 PEST CONTROL COMPANY THAT CONTAINS THE FOLLOWING
 STATEMENT: THE BUILDING HAS RECEIVED A COMPLETE
 TREATMENT FOR THE PREVENTION OF SUBTERRANEAN TERMITES.
 TREATMENT IS IN ACCORDANCE WITH RULES AND LAWS
 ESTABLISHED BY THE FLORIDA DEPARTMENT OF AGRICULTURE
 AND CONSUMER SERVICES.
  
 14. FOOTING TE IN THE SCHEDULE ON SHEET S-4.00A IS 1
 FOOT THICK AND ACCORDING TO SECTION 1/S-3.00A IS A
 MONOLITHIC SLAB. DRAWING 1/S-3.00A,B AND C SHOWS THE
 EXTERIOR GRADE LEVEL WITH THE FINISH FLOOR. IN ORDER TO
 BE A MINIMUM OF 12" BELOW GRADE AND 4" ABOVE GRADE, THE
 FOOTING IS REQUIRED TO BE A MINIMUM OF 16" THICK.
 FBC-R403.1.4 MINIMUM DEPTH. EXTERIOR FOOTINGS SHALL BE
 PLACED NOT LESS THAN 12 INCHES (305 MM) BELOW THE
 UNDISTURBED GROUND SURFACE. FBC-R404.1.6 HEIGHT ABOVE
 FINISHED GRADE. CONCRETE AND MASONRY FOUNDATION WALLS
 SHALL EXTEND ABOVE THE FINISHED GRADE ADJACENT TO THE
 FOUNDATION AT ALL POINTS A MINIMUM OF 4 INCHES (102 MM)
 WHERE MASONRY VENEER IS USED AND A MINIMUM OF 6 INCHES
 (152 MM) ELSEWHERE.
  
 15. DETAIL HOW THE RAIN WATER FROM THE SLOPED ROOF WILL
 BE DIVERTED AROUND THE ENTRY TOWERS SHOWN FOR MODELS B
 AND C. IF A ROOF CRICKET WILL BE USED PROVIDE DETAILS.
 FBC-R903.2.2 & FBC 107.2.1
  
 16. THE WIND DESIGN PRESSURES FOR COMPONENTS AND
 CLADDING ON SHEET S-4.00A APPEAR TO HAVE ERRORS. THE
 NEGATIVE PRESSURES FOR ROOF ZONES 2 AND 3 SHOULD NOT BE
 THE SAME. THE PRESSURES ALSO APPEAR TO BE HIGH. PROVIDE
 THE CALCULATIONS USED TO DETERMINE THESE PRESSURES. FBC
 107.2.1.2 SINCE THE WINDOW AND DOOR PRESSURES ON THE
 PRODUCT APPROVALS ARE BASED ON VASD AND IN ORDER TO
 AVOID CONFUSION, PLEASE PROVIDE A COMPONENT AND
 CLADDING SCHEDULE WITH 132MPH EXPOSURE C NOMINAL VASD
 PRESSURES. FBC 301.2.1.3
  
 17. IT IS NOT CLEAR ON THE ROOF FRAMING PLAN
 S-2.01A,B,C WHICH ANCHORS ARE SPECIFIED FOR EACH OF THE
 TRUSSES. PLEASE REVIEW AND CLARIFY. FBC 107.2.1
  
 18. SUBMIT TWO SETS OF SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS FOR THE OUTDOOR RANGE AT THE OUTDOOR
 SUMMER KITCHEN. FBC 107.2.1
  
 19. ) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT
 APPROVALS FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT
 ROOFING MATERIALS, WINDOW/GLASS TYPES, STRUCTURAL
 MULLIONS AND EXTERIOR DOOR TYPES.
  
 20. SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE OFF
 RIDGE ROOF VENTS (NOA 17-1031.03). FBC 107.3.4
  
 21. THE PRODUCT APPROVAL NUMBERS LISTED ON THE PLANS
 FOR THE OVERHEAD GARAGE DOORS ARE FL NUMBERS NOT NOAS.
 PLEASE CORRECT.
  
 22. THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 ENTRY DOOR HAVE A DIFFERENT NUMBER THAN THE ONE
 SPECIFIED ON THE PLANS. FL17-1031.03 IS LISTED ON THE
 PLANS. THIS IS A NOA NUMBER NOT AN FL. THE PRODUCT
 APPROVAL SUBMITTED IS FL15037.3. PLEASE COORDINATE. FBC
 107.2.1
  
 23. NONE OF THE THREE OPTIONS FOR THIS MODEL USES METAL
 ROOFING. REMOVE REFERENCE TO METAL ROOFING FROM PLANS.
 INDICATE THE CEMENT ROOF TILE AND ATTACHMENT METHOD
 THAT WILL BE USED BY MARKING THE APPROPRIATE
 INFORMATION ON THE PLANS. FBC 107.2.1 IF AN ADHESIVE
 WILL BE USED, SUBMIT THE PRODUCT APPROVAL FOR IT. FBC
 107.3.4 IF A MORTAR OR ADHESIVE SET IS USED SUBMIT THE
 PRODUCT APPROVAL FOR THE UNDERLAYMENT TO SHOW THAT IT
 WILL MEET WINDLOADS. SEE INSTALLATION NOTE 6.2 ON PAGE
 5 OF THE TILE PRODUCT APPROVAL.
  
 24. SUBMIT TWO SETS OF SIGNED AND SEALED TRUSS DRAWINGS
 AND TRUSS LAYOUT PLANS THAT HAVE BEEN REVIEWED AND
 APPROVED BY THE DESIGNER OF RECORD FOR THE PROJECT.
 FBC-R802.10
  
 25. PRODUCT APPROVALS WERE SUBMITTED FOR FIXED WINDOWS
 (NOA NO. 17-1212.13) AND STRUCTURAL MULLIONS (NOA NO.
 17-1212.24) AND NEITHER OF THESE ARE USED FOR THIS
 PROJECT. PLEASE CLARIFY. FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  