Plan Review Notes
Plan Review Notes For Permit 18041007
Permit Number 18041007
Review Stop E
Sequence Number 1
Notes
Date Text
2018-05-09 15:33:05CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLAN NEEDS TO BE CLEAR AND LEGIBLE. THE ADDRESS
 BLOCK IS UNREADABLE, MANY OTHER ITEMS DIFFICULT TO
 READ. WPB FBC 107.2.1.3
 2. THE NEC AND FBC SPECIFIED FOR DESIGN IS NOT THE
 CURRENT CODE. PROVIDE CORRECTION. FBC PREFACE (ALSO SEE
 CURRENT CODES ABOVE)
 3. ELECTRICAL PANEL MUST HAVE PROPRER CLEARANCE.
 PROVIDE CORRECTION. NEC 110.26
 4. PROVIDE AFCI PROTECTION FOR ANY BRANCH CIRCUIT
 MODIFICATIONS. NEC 210.12(B)
 5. PROVIDE TAMPER RESISTANT RECEPTACLES. NEC 406.12
 6. LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE
 SUITABLE FOR DAMP LOCATIONS. PROVIDE CORRECTION. NEC
 410.10(D)
 7. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC 210.8(D)
 8. RECEPTACLES IN KITCHEN REQUIRE GFCI AND AFCI
 PROTECTION. PROVIDE CORRECTION. NEC 210.8
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  