Plan Review Notes For Permit 18040945 |
Permit Number |
18040945 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2018-05-26 08:01:42 | 1) SUBMIT TWO LEGIBLE COPIES OF THE POOL PUMP CURVE IN | | ORDER TO CONFIRM THE MAXIMUM FLOW AT THE CALCULATED | | TDH.. WPB AMEND. TO FBC SEC. 107.2.1. 2ND REQUEST. | | 2) IDENTIFY ON A LEGIBLE POOL PUMP CURVE THE SPECIFIC | | PUMP THAT IS BEING INSTALLED. WPB AMEND. TO FBC SEC. | | 107.2.1. THE 2.7 HP PUMP LISTED IN THE EQUIPMENT SPECS | | IS NOT LISTED ON THE SUBMITTED PUMP CURVE. 2ND REQUEST. | | 3) SHT. 2 OF 4 - THERE ARE TWO BOXES ON THE PLAN, ONE | | FOR THE POOL AND ONE FOR THE FEATURE THAT STILL NOTE | | THAT SYSTEM FLOW RATE HAS BEEN DETERMINED BY THE | | MAXIMUM FLOW RATE FROM THE PUMP CURVE. THIS IS NO | | LONGER PERMITTED PER APSP 7-2013 SEC. 4.4.9.. DELETE | | THIS FROM THE PLANS.AND NOTE THAT THE SYSTEM FLOW RATE | | IS BASED ON THE TDH. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | | | | | |
|