Plan Review Notes
Plan Review Notes For Permit 18040945
Permit Number 18040945
Review Stop P
Sequence Number 1
Notes
Date Text
2018-05-13 11:12:351) PER APSP 7 -2013, THE MAXIMUM FLOW RATE FROM THE
 MANUFACTURER'S PUMP CURVE CAN NO LONGER BE USED TO
 DETERMINE MAXIMUM SYSTEM FLOW RATE. THE NEW CODE
 SEPARATES METHODS FOR DETERMINING MAXIMUM SYSTEM FLOW
 RATE INTO TWO CATEGORIES; UNSECURED SYSTEMS (TYPICAL
 RESIDENTIAL SYSTEMS) AND SECURED SYSTEMS (TYPICAL
 COMMERCIAL SYSTEMS). SUBMIT TOTAL TOTAL DYNAMIC HEAD
 CALCULATIONS.
 2) SUBMIT TWO LEGIBLE COPIES OF THE POOL PUMP CURVE.
 WPB AMEND. TO FBC SEC. 107.2.1.
 3) IDENTIFY ON A LEGIBLE POOL PUMP CURVE THE SPECIFIC
 PUMP THAT IS BEING INSTALLED. WPB AMEND. TO FBC SEC.
 107.2.1.
 4) A GAS PERMIT APPLICATION HAS BEEN SUBMITTED IN THE
 POOL PACKAGE BUT THERE ARE NO GAS PLANS. CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  