2018-04-26 17:54:341ST REVIEW FBC-2014 MECHANICAL
 PERMIT #18040940
 4/26/18
  
 PLAN REVIEW
  
 1) SHEET M0.3: PLEASE PROVIDE REVISED AC COOLING AND
 HEATING CALCULATIONS FOR THE NEW LARGER TRANE RTU'S 6,
 7, 8, &10- SECTUION C403.2.1 FBC-14 ENERGY
 CONSERVATION.
  
 2) M1.1: THE RETURN AIR TRANSFER FROM THE STORAGE ROOM
 MAY BE PROHIBITED DEPENDING ON WHAT MATERIALS OR
 EQUIPMENT ARE IN THE ROOM- SEE SECTION 918,6 (1, 2, &
 3),
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  