Notes |
Date |
Text |
2018-04-26 17:54:34 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #18040940 | | 4/26/18 | | | | PLAN REVIEW | | | | 1) SHEET M0.3: PLEASE PROVIDE REVISED AC COOLING AND | | HEATING CALCULATIONS FOR THE NEW LARGER TRANE RTU'S 6, | | 7, 8, &10- SECTUION C403.2.1 FBC-14 ENERGY | | CONSERVATION. | | | | 2) M1.1: THE RETURN AIR TRANSFER FROM THE STORAGE ROOM | | MAY BE PROHIBITED DEPENDING ON WHAT MATERIALS OR | | EQUIPMENT ARE IN THE ROOM- SEE SECTION 918,6 (1, 2, & | | 3), | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|