Plan Review Notes
Plan Review Notes For Permit 18040933
Permit Number 18040933
Review Stop B
Sequence Number 1
Notes
Date Text
2018-04-28 12:07:22****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FBC BUILDING 2010 1609, DELEGATED ENGINEER (STEPHEN
 WARTER, PE) STATES THAT DESIGN PRESSURES WERE OBTAINED
 FROM THE WIND TUNNEL REPORT, WORST CASE OF +117, -223
 PSF. SEE PAGE3 OF THE REPORT WHICH STATES:
  
 DESIGN PRESSURES FOR THE ROOF AND SOFFIT SIDE . . . DO
 NOT INCLUDE ANY ALLOWANCE FOR INTERNAL PRESSURE. . . .
 DEPENDING ON THE CONSTRUCTION OF THE ROOF SYSTEM,
 INCLUSION OF THE INTERNAL PRESSURE MAY OR MAY NOT BE
 APPROPRIATE. THEREFORE, THE SUPPLIER OF THE ROOFING
 SYSTEM SHOULD CONSIDER IF AN INTERNAL PRESSURE SHOULD
 BE ADDED TO THE PRESSURE VALUES IN FIGURE 5."
  
 ALTHOUGH IT DOES NOT APPEAR THAT INTERNAL PRESSURE
 SHOULD BE ADDED, IT APPEARS THAT THIS DETERMINATION IS
 THE RESPONSIBILITY OF THE DELEGATED ENGINEER. THIS
 COMMENT MAY BE ADDRESSED WITH A STATEMENT IN A
 DIGITALLY SIGNED AND SEALED LETTER SENT VIA EMAIL TO
 [email protected]. PLEASE REFERENCE THIS SUBMITTAL NUMBER
 (18040933) IN THE SUBJECT LINE.
  
  
  
  