Plan Review Notes For Permit 18040933 |
Permit Number |
18040933 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-04-28 12:07:22 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. FBC BUILDING 2010 1609, DELEGATED ENGINEER (STEPHEN | | WARTER, PE) STATES THAT DESIGN PRESSURES WERE OBTAINED | | FROM THE WIND TUNNEL REPORT, WORST CASE OF +117, -223 | | PSF. SEE PAGE3 OF THE REPORT WHICH STATES: | | | | DESIGN PRESSURES FOR THE ROOF AND SOFFIT SIDE . . . DO | | NOT INCLUDE ANY ALLOWANCE FOR INTERNAL PRESSURE. . . . | | DEPENDING ON THE CONSTRUCTION OF THE ROOF SYSTEM, | | INCLUSION OF THE INTERNAL PRESSURE MAY OR MAY NOT BE | | APPROPRIATE. THEREFORE, THE SUPPLIER OF THE ROOFING | | SYSTEM SHOULD CONSIDER IF AN INTERNAL PRESSURE SHOULD | | BE ADDED TO THE PRESSURE VALUES IN FIGURE 5." | | | | ALTHOUGH IT DOES NOT APPEAR THAT INTERNAL PRESSURE | | SHOULD BE ADDED, IT APPEARS THAT THIS DETERMINATION IS | | THE RESPONSIBILITY OF THE DELEGATED ENGINEER. THIS | | COMMENT MAY BE ADDRESSED WITH A STATEMENT IN A | | DIGITALLY SIGNED AND SEALED LETTER SENT VIA EMAIL TO | | [email protected]. PLEASE REFERENCE THIS SUBMITTAL NUMBER | | (18040933) IN THE SUBJECT LINE. | | | | | | | | |
|