2018-05-01 10:43:391) THE PAPERWORK SUBMITTED FROM TIE DOWN ENGINEERING IS
 UNACCEPTABLE. COPIES OF SIGNED AND SEALED ENGINEERING
 PLANS OR DOCUMENTS VIOLATES FL. ADMIN. CODE RULE
 61G15-23.001.
 61G15-23.001 SIGNATURE, DATE AND SEAL SHALL BE AFFIXED.
 (1) A PROFESSIONAL ENGINEER SHALL SIGN, DATE AND SEAL:
 (A) ALL FINAL PLANS, PRINTS, SPECIFICATIONS, REPORTS,
 OR OTHER DOCUMENTS PREPARED OR ISSUED BY THE LICENSEE
 AND BEING FILED FOR PUBLIC RECORD
  
 61G15-23.003 PROCEDURES FOR PHYSICALLY SIGNING AND
 SEALING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS.
 ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED IN
 ACCORDANCE WITH THE PROVISIONS OF SECTION 471.025,
 F.S., AND RULE 61G15-23.001, F.A.C. MAY BE PHYSICALLY
 SIGNED, DATED AND SEALED AS PROVIDED HEREIN BY THE
 PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
 (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE
 LICENSEE'S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE'S SIGNATURE SHALL NOT BE
 USED.
 (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY
 CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY
 OVERLAPPING THE LICENSEE'S SIGNATURE ON EACH PAGE
 REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL
 NOT RENDER THE SIGNATURE ILLEGIBLE.
 NOTE: THIS ISSUE HAS BEEN BROUGHT TO THE ATTENTION OF
 STATIC ELECTRICITY ON NUMEROUS OCCASSIONS YET THE
 CONTINUANCE OF SUBMITTAL OF THESE DOCUMENTS CONTINUES.
 THE LICENSE FOR THIS ENGINEER HAS BEEN NULL AND VOID
 SINCE 2015. THESE DOCUMENTS HAVE BEEN UNACCEPTABLE IN
 THE PAST, ARE UNACCEPTABLE IN THE PRESENT AND WILL BE
 UNACCEPTABLE IN THE FUTURE.
  
 2) THE GAS DRAWING REFERENCES GAS SIZING TABLE 402.4
 (36) WHICH IS FOR A 2 PSI SYSTEM BUT THE GAS DRAWING
 DOES NOT SHOW THE 2 PSI SYSTEM. THE ONLY REFERENCE IS
 TO 10 PSI SYSTEM. CLARIFY.
  
 3) YOU HAVE SUBMITTED SIX DIFFERENT GAS SIZING TABLES
 FROM GASTITE IN ADDITION TO REFERENCING A TABLE ON THE
 GAS PLAN FOR A 2 PSI SYSTEM FROM THE 2017 FBC-FUEL GAS
 CODE. AT THIS POINT, I HAVE NO IDEA WHAT TABLE(S) YOU
 ARE USING TO SIZE THIS SYSTEM. IDENTIFY WHICH SIZING
 TABLE IS BEING USED FOR EACH PRESSURE. REMOVE ANY
 SIZING TABLE NOT BEING USED.WPB AEND. TO FBC SEC.
 107.2.1.
  
 4) PROVIDE THE SIZE OF THE HOLD-DOWN CABLES/STRAPS FOR
 THE TANK AND THE TYPE AND LENGTH OF GROUND ANCHORS TO
 BE INSTALLED TO PREVENT FLOTATION. NFPA 58 SEC.
 6.6.1.6.
  
 5) IDENTIFY THE LOCATION OF THE FIRST STAGE REGULATOR
 ON THE PLANS.
  
 6) SUBMIT ALL THE PAGES FOR THE INSTALLATION
 INSTRUCTIONS FOR THE REGULATORS. 2017 FBC-FUEL GAS SEC.
 410.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW