Plan Review Notes
Plan Review Notes For Permit 18040925
Permit Number 18040925
Review Stop G
Sequence Number 2
Notes
Date Text
2018-06-05 06:33:311)THE GAS DRAWING REFERENCES GAS SIZING TABLE 402.4
 (36) WHICH IS FOR A 2 PSI SYSTEM BUT THE GAS DRAWING
 DOES NOT SHOW THE 2 PSI SYSTEM. THE ONLY REFERENCE IS
 TO 10 PSI SYSTEM. CLARIFY.
  
 2) PROVIDE DETAILS FOR THE ANCHORING OF THE LP TANK TO
 PREVENT FLOTATION.PROVIDE THE SIZE OF THE HOLD-DOWN
 CABLES/STRAPS FOR THE TANK AND THE TYPE AND LENGTH OF
 GROUND ANCHORS TO BE INSTALLED TO PREVENT FLOTATION.
 NFPA 58 SEC. 6.6.1.6.
  
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS/INSTALLATION
 INSTRUCTIONS FOR BOTH TYPE OF REGULATORS. 2017 FBC-FUEL
 GAS SEC. 410.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  
  