Plan Review Notes
Plan Review Notes For Permit 18040923
Permit Number 18040923
Review Stop E
Sequence Number 1
Notes
Date Text
2018-04-24 07:08:03ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL OR THE
 ELECTRICAL CONTRACTOR QUALIFIER. IF THERE IS NOT ANY
 ELECTRICAL WORK INCLUDED WITH THIS PERMIT, STATE
 THAT ON PLAN. FS 471.003(2)(H); 471.025; FBC 107.2.1,
 107.3.5
  
 PLAN SUBMITTED SHOWS ONLY "DECORATIVE LIGHT". PLEASE
 PROVIDE, CONDUIT SIZE, WIRE SIZE, CIRCUIT NUMBER, ETC.
  
 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE
 CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE APPLICABLE
 TO COMPLY WITH CODE. NEC 210.8, 210.12,
 215.5, 408.4; FBC RE3706.2, RE3902
  
 3. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND VALUE
 OF WORK, TO INCLUDE ALL MATERIALS AND LABOR.
 FBC 109.3
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN
 REVIEW COMMENTS. WHEN RESUBMITTING, IT IS HELPFUL TO
 PROVIDE A RESPONSE LETTER ADDRESSING
 EACH ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO
 THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 5TH
 EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 5TH EDITION, PART
 VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 [email protected]
 561-657-1653