2018-04-24 07:08:03 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND |
| SEALED BY A LICENSED DESIGN PROFESSIONAL OR THE |
| ELECTRICAL CONTRACTOR QUALIFIER. IF THERE IS NOT ANY |
| ELECTRICAL WORK INCLUDED WITH THIS PERMIT, STATE |
| THAT ON PLAN. FS 471.003(2)(H); 471.025; FBC 107.2.1, |
| 107.3.5 |
| |
| PLAN SUBMITTED SHOWS ONLY "DECORATIVE LIGHT". PLEASE |
| PROVIDE, CONDUIT SIZE, WIRE SIZE, CIRCUIT NUMBER, ETC. |
| |
| 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE |
| CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE APPLICABLE |
| TO COMPLY WITH CODE. NEC 210.8, 210.12, |
| 215.5, 408.4; FBC RE3706.2, RE3902 |
| |
| 3. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND VALUE |
| OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. |
| FBC 109.3 |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN |
| REVIEW COMMENTS. WHEN RESUBMITTING, IT IS HELPFUL TO |
| PROVIDE A RESPONSE LETTER ADDRESSING |
| EACH ITEM ALONG WITH THE CITY RESUBMITTAL FORM. |
| ADDITIONALLY, INSERT CORRECTED PAGES INTO |
| THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |
| CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 5TH EDITION |
| FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 5TH |
| EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 5TH EDITION, PART |
| VIII ELECTRICAL |
| NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| V/R, |
| |
| FRANK GIAQUINTO |
| ELECTRICAL INSPECTOR |
| ELECTRICAL PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| DEVELOPMENT SERVICES |
| [email protected] |
| 561-657-1653 |