2018-10-17 15:57:58 | 3RD REVIEW FBC-2017 MECHANICAL |
| PERMIT #18040836 |
| 10/17/18 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) REFER TO SECTION 306.5 AND PROVIDE AN INTERIOR OR |
| EXTERIOR MEANS OF ACCESS TO THE ROOFTOP MECHANICAL |
| EQUIPMENT. PLEASE NOTE THAT ACCESS SHALL NOT REQUIRE |
| THE USE OF PORTABLE LADDERS. |
| |
| 2) SHEET M-1: THE PLAN INDICATES "CONTINUOUS" EXHAUST |
| VENTILATION TO BE CONTROLLED BY A SWITCH, HOWEVER THE |
| DEFINITION OF CONTINUOUS INDICATES THE FUNCTION TO BE |
| UNINTERRUPTED. PLEASE PROVIDE A VENTILATION SYSTEM THAT |
| IS IN COMPLIANCE. |
| |
| 3) REFER TO PAGE 2 OF THE MITSUBISHI CONDENSER |
| INSTALLATION SUBMITTAL. THE DETAIL INDICATES THAT THE |
| ROOF STAND IS TO BE PROVIDED "BY OTHERS". PLEASE SUBMIT |
| A VALID FL. PRODUCT APPROVAL OR A MIAMI-DADE NOA FOR |
| THE STAND. |
| |
| 4) THE REQUESTED ENGINEERING FOR INSTALLATION OF THE |
| ROOFTOP EXHAUST FAN WAS NOT PROVIDED- SECTION 107.2.1 |
| WPB. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |