2018-08-09 08:38:05 | 2ND REVIEW FBC-2017 MECHANICAL |
| PERMIT #18040836 |
| 8/9/18 |
| |
| CODES IN EFFECT: |
| FBC BC- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC MC- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC RE- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC-SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET M-1: THE PARKING GARAGE EXHAUST SYSTEM SHALL |
| EITHER OPERATE CONTINUOUSLY OR INTERMITTENTLY BY MEANS |
| OF CO AND N02 SENSORS- SEE SECTIONS 404.1, 404.2, 404.3 |
| AND 502.13 FBC M. PLEASE PROVIDE A SEQUENCE OF |
| OPERATION THAT IS IN COMPLIANCE. |
| |
| 2) M-3: THE RTU INSTALLATION ENGINEERING FROM RHEEM |
| THAT WAS SUBMITTED DOES NOT MATCH THE ENGINEERING SHOWN |
| ON SHEET M-3, AND NEITHER DETAIL PROVIDES A MEANS OF |
| ATTACHING THE CURB TO THE ROOF STRUCTURE. PLEASE NOTE |
| THAT THE RHEEM ENGINEERING DOCUMENT DOES NOT LIST THE |
| RHEEM MODEL NO. RACA IN THE UNIT APPLICABILITY TABLE. |
| PLEASE PROVIDE COMPLETE ENGINEERING ON M-3 INCLUDING |
| THE WINDLOAD DESIGN CRITERIA AS OULTINED IN SECTION |
| 1609 FBC-BC. |
| |
| 3) PROVIDE ENGINEERING FOR INTALLATION OF THE ROOF |
| EXHAUST FAN EF-2, AND VERIFY THERE IS A 42" PARAPET BY |
| THE FAN BECAUSE IT IS WITHIN THE REQUIRED 10' MINIMUM |
| CLEARANCE TO THE ROOF EDGE- SEE SECTIONS 301.15 AND |
| 304.11 FBC M. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |