2018-05-26 08:26:351ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE OUTLET OF THE TOILET PAPER DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR. PER FBC ACC 604.7
  
 2. PLEASE PROVIDE A DETAIL FOR THE EMERGENCY SCUPPER
 AND SHOW COMPLIANCE WITH FBC 1503.4.2.1 OVERFLOW
 SCUPPERS. WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW
 WATER IS NOT PROVIDED, OVERFLOW SCUPPERS SHALL BE
 PLACED IN WALLS OR PARAPETS NOT LESS THAN 2 INCHES NOR
 MORE THAN 4 INCHES ABOVE THE FINISHED ROOF COVERING AND
 SHALL BE LOCATED AS CLOSE AS PRACTICAL TO REQUIRED
 VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND PARAPET
 SCUPPERS. AN OVERFLOW SCUPPER SHALL BE SIZED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING.
  
 3. SHT. P-1 REFERENCES THE CIVIL DRAWING FOR THE
 LOCATION AND SIZE OF THE GREASE INTERCEPTOR NO CIVIL
 DRAWING WAS INCLUDED IN THIS PLAN SET. PLEASE PROVIDE
 CIVIL DRAWING SHOWING SIZE AND LOCATION OF THE GREASE
 INTERCEPTOR , WATER METER AND BACKFLOW. PER WPB AMEND
 TO FBC 107.2.1
  
 4. PROVIDE SIZING CALCULATIONS FOR THE GREASE
 INTERCEPTOR. PER WPB AMEND TO FBC 107.2.1
  
 5. PLACE NOT ON PLAN TEMPERED WATER SHALL BE DELIVERED
 FROM LAVATORIES AND GROUP WASH FIXTURES LOCATED IN
 PUBLIC TOILET FACILITIES PROVIDED FOR CUSTOMERS,
 PATRONS AND VISITORS. TEMPERED WATER SHALL BE DELIVERED
 THROUGH AN APPROVED WATER-TEMPERATURE LIMITING DEVICE
 THAT CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL
 416.5
  
 6. THE FLOOR SINK SHALL BE EQUIPPED WITH A TRAP PRIMER
 VALVE. PER FBC PL 1002.4.1
  
 7. WHAT IS THE FLOOR SINK BEING USED TO DRAIN PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 8. WHAT IS THIS SPACE GOING TO BE USED FOR IS THERE
 GOING TO BE COOKING OR FOOD PREP ON PROPERTY OR WILL IT
 BE USED TO STORE COOKING EQUIPMENT WITH ANY KIND OF
 FLAMMABLE GASES, LIQUIDS OR SOLID FUEL PLEASE CLARIFY.
 PER WPB AMEND TO FBC 107.2.1
  
 9. ON THE COVER SHEET THE CODE REVIEW LIST THE 2014
 PLUMBING AND ACCESSIBILITY THIS PROJECT SHALL COMPLY
 WITH FBC PLUMBING AND ACCESSIBILITY 2017 6TH EDITION.
 PLEAS CLARIFY PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  