2018-05-26 08:26:35 | 1ST REVIEW: FBC 2017 6TH EDITION |
| |
| PLUMBING COMMENTS: |
| |
| 1. THE OUTLET OF THE TOILET PAPER DISPENSER SHALL BE 15 |
| INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH |
| FLOOR. PER FBC ACC 604.7 |
| |
| 2. PLEASE PROVIDE A DETAIL FOR THE EMERGENCY SCUPPER |
| AND SHOW COMPLIANCE WITH FBC 1503.4.2.1 OVERFLOW |
| SCUPPERS. WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW |
| WATER IS NOT PROVIDED, OVERFLOW SCUPPERS SHALL BE |
| PLACED IN WALLS OR PARAPETS NOT LESS THAN 2 INCHES NOR |
| MORE THAN 4 INCHES ABOVE THE FINISHED ROOF COVERING AND |
| SHALL BE LOCATED AS CLOSE AS PRACTICAL TO REQUIRED |
| VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND PARAPET |
| SCUPPERS. AN OVERFLOW SCUPPER SHALL BE SIZED IN |
| ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING. |
| |
| 3. SHT. P-1 REFERENCES THE CIVIL DRAWING FOR THE |
| LOCATION AND SIZE OF THE GREASE INTERCEPTOR NO CIVIL |
| DRAWING WAS INCLUDED IN THIS PLAN SET. PLEASE PROVIDE |
| CIVIL DRAWING SHOWING SIZE AND LOCATION OF THE GREASE |
| INTERCEPTOR , WATER METER AND BACKFLOW. PER WPB AMEND |
| TO FBC 107.2.1 |
| |
| 4. PROVIDE SIZING CALCULATIONS FOR THE GREASE |
| INTERCEPTOR. PER WPB AMEND TO FBC 107.2.1 |
| |
| 5. PLACE NOT ON PLAN TEMPERED WATER SHALL BE DELIVERED |
| FROM LAVATORIES AND GROUP WASH FIXTURES LOCATED IN |
| PUBLIC TOILET FACILITIES PROVIDED FOR CUSTOMERS, |
| PATRONS AND VISITORS. TEMPERED WATER SHALL BE DELIVERED |
| THROUGH AN APPROVED WATER-TEMPERATURE LIMITING DEVICE |
| THAT CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL |
| 416.5 |
| |
| 6. THE FLOOR SINK SHALL BE EQUIPPED WITH A TRAP PRIMER |
| VALVE. PER FBC PL 1002.4.1 |
| |
| 7. WHAT IS THE FLOOR SINK BEING USED TO DRAIN PLEASE |
| CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| |
| 8. WHAT IS THIS SPACE GOING TO BE USED FOR IS THERE |
| GOING TO BE COOKING OR FOOD PREP ON PROPERTY OR WILL IT |
| BE USED TO STORE COOKING EQUIPMENT WITH ANY KIND OF |
| FLAMMABLE GASES, LIQUIDS OR SOLID FUEL PLEASE CLARIFY. |
| PER WPB AMEND TO FBC 107.2.1 |
| |
| 9. ON THE COVER SHEET THE CODE REVIEW LIST THE 2014 |
| PLUMBING AND ACCESSIBILITY THIS PROJECT SHALL COMPLY |
| WITH FBC PLUMBING AND ACCESSIBILITY 2017 6TH EDITION. |
| PLEAS CLARIFY PER WPB AMEND TO FBC 107.2.1 |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |