2018-05-21 17:44:04 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #18040836 |
| 5/21/18 |
| |
| CODES IN EFFECT: |
| FBC BC- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC MC- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC RE- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC-SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| |
| 1) SHEETS A300 & M-1: THE OUTSIDE INTAKE APPEARS TO BE |
| WITHIN THE 10' MINIMUM REQUIRED CLEARANCE TO THE |
| DRIVEWAY- SEE SECTION 401.4(2) FBC MC. |
| |
| 2) M-100: PROVIDE A FLORIDA PRODUCT APPROVAL OR |
| MIAMI-DADE NOA FOR THE LOUVER PER FAC RULE 9N-3. SUBMIT |
| SPECS FOR THE LOUVER SHOWING COMPLIANCE WITH 401.5 FBC |
| MC. |
| |
| 3) M-300: PROVIDE THE WIND LOAD DESGIN CRITERIA FOR TIE |
| DOWN OF THE RTU AND CURB- SEE SECTION 1609 FBC BC. |
| |
| 4) M-300: CURB BOLT INFORMATION NOT PROVIDED ON |
| MECHANICAL OR STRUCTURAL PLANS. PROVIDE THE TYPE AND |
| SIZE OF BOLT, DEPTH OF EMBEDMENT, AND SPACING OF BOLTS. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |