2018-06-12 17:38:24 | BUILDING REVIEW COMMENTS |
| CODE: FBC 6TH EDITION (2017). |
| |
| 1-IMPACT FEES |
| BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES |
| MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE |
| SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM |
| BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH |
| THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT |
| MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE |
| THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL |
| PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025. |
| |
| 2- PROVIDE SITE PLAN THAT INCLUDES COMPLETE INFORMATION |
| FOR DRAINAGE AS REQUIRED BY SEC. 107.2.5 CITY |
| AMENDMENTS. |
| |
| SEC. 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS |
| SUBMITTED WITH THE APPLICATION FOR PERMIT SHALL BE |
| ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE THE SIZE |
| AND LOCATION OF NEW CONSTRUCTION AND EXISTING |
| STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE |
| ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED |
| GRADES, DEPICTING THE PROPOSED LOT DRAINAGE AND, AS |
| APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN |
| FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE |
| WITH AN ACCURATE AND INCLUDED ON A BOUNDARY LINE |
| SURVEY. IN THE CASE OF DEMOLITION, THE SITE PLAN SHALL |
| SHOW CONSTRUCTION TO BE DEMOLISHED AND THE LOCATION AND |
| SIZE OF EXISTING STRUCTURES AND CONSTRUCTION THAT ARE |
| TO REMAIN ON THE SITE OR PLOT. THE BUILDING OFFICIAL IS |
| AUTHORIZED TO WAIVE OR MODIFY THE REQUIREMENT FOR A |
| SITE PLAN WHEN THE |
| APPLICATION FOR PERMIT IS FOR ALTERATION OR REPAIR OR |
| WHEN OTHERWISE WARRANTED. |
| |
| 3- SHEET G100: |
| A) CODE REVIEW INFORMATION REFERENCES FLORIDA |
| ACCESSIBILITY CODE 2014 AND FLORIDA PLUMBING CODE 2014. |
| THE CURRENT CODE IS THE 2017 CODE. REVISE AS REQUIRED. |
| CHAPTER 553 F.S. |
| |
| B) OCCUPANCY CLASSIFICATION IS NOT CLEAR. CODE REVIEW |
| INFORMATION SPECIFIES BUSINESS AND LIGHT STORAGE S-2 |
| OCCUPANCIES, WHILE INFORMATION ON SHEET S301 SPECIFIES |
| OCCUPANCY CLASSIFICATION F-1. REVISE AS REQUIRED TO |
| MATCH. SEC. 302.1 FBC. |
| |
| C) CONSTRUCTION TYPE IS NOT CLEAR. CODE REVIEW |
| SPECIFIES CONSTRUCTION TYPE III-B, WHILE INFORMATION ON |
| SHEET S301 SPECIFIES CONSTRUCTION TYPE II. REVISE AS |
| REQUIRED. SEC. 601.1 FBC. |
| |
| D) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR 2 |
| HOUR FIRE RATED EXTERIOR WALLS ASSEMBLY AS REQUIRED TO |
| COMPLY WITH SEC. 602.3 FBC FOR TYPE III-B CONSTRICTION. |
| COORDINATE WITH ITEM #3D ABOVE. |
| |
| E) OCCUPANCY LOAD SPECIFIED ON CODE REVIEW IS NOT CLEAR |
| AND IT DOESN'T MATCH INFORMATION SHOWN ON FLOOR PLANS |
| ON SHEET A-300. IN ADDITION, NEED TO SPECIFY THE |
| OCCUPANT LOAD OF THE MEZZANINE. SEC. 1004.1 FBC AND |
| TABLE 1004.1.2 FBC. |
| |
| F)EGRESS INFORMATION IN CODE REVIEW IS INCOMPLETE AND |
| NEED TO BE UPDATED. PROVIDE THE MAXIMUM TRAVEL DISTANCE |
| (INCLUDING MEZZANINE) AND UPDATE CITED TABLES. SEE 2017 |
| FBC FOR CORRECT TABLES AND SECTIONS. |
| PROVIDE MAXIMUM TRAVEL DISTANCE ON PLANS, INCLUDING |
| FROM MEZZANINE. NOTE: SEE SEC. 1017.3 FBC FOR |
| MEASUREMENT OF TRAVEL DISTANCE. |
| |
| 4- SHEET S-300: |
| A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR ALL |
| THE TIE BEAMS OF TWO STORY REINFORCED CONCRETE BLOCK |
| WALL. SEC. 1604.1 FBC. |
| |
| B) IT LOOKS LIKE THE ANCHORS SPECIFIED TO SUPPORT |
| (2)2X6 STRUCTURAL WOOD LEDGER FOR THE MEZZANINE FLOOR |
| TRUSSES MIGHT NOT BE ADEQUATE TO SUPPORT ALL THE LIVE |
| AND DEAD LOADS. THIS MEZZANINE IS USED FOR STORAGE. SEE |
| TABLE 1607.1 FBC FOR REQUIRED LIVE LOADS. PROVIDE |
| ENGINEERING ANALYSIS SHOWING COMPLIANCE WITH ALL THE |
| DEAD AND LIVE LOADS. COORDINATE WITH COMMENTS ON SHEET |
| S3001. |
| |
| C) ACCORDING TO PLANS SUBMITTED, IT LOOKS LIKE THE WEST |
| TWO STORY HIGH WALL MAY NOT HAVE ENOUGH VERTICAL |
| REINFORCEMENT. PROVIDE COMPLETE DETAILS AND |
| SPECIFICATIONS (INCLUDING LOCATION) FOR VERTICAL |
| REINFORCEMENT SHOWING HOW THE WALL WILL RESIST ALL THE |
| LATERAL LOADS. SEC. 107.2.1.2 CITY AMENDMENTS. |
| |
| D) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| ROOF TRUSSES AND FLOOR TRUSSES STRUCTURAL CONNECTORS. |
| SEC. 1601.1 FBC. (NOTE: CLARIFY WHY ALL THE BUILDING |
| SECTIONS SHOW BAR JOISTS INSTEAD OF WOOD TRUSSES). |
| |
| E) CLEARLY SPECIFY FOOTING SIZES. SEC. 1801.2 FBC. |
| NOTE: COORDINATE WITH ACCESSIBLE ENTRY TO AVOID |
| CONFLICTS. ALSO, TAKE INTO CONSIDERATION THE 12" |
| REQUIREMENT BELOW GRADE. |
| |
| 5- SHEET S-301: |
| A) DESIGN NOTES REFERENCE THE 2014 FBC. THE CURRENT |
| CODE IS 2017, 6TH EDITION. REVISE AS REQUIRED. CHAPTER |
| 553 F.S. |
| |
| B) REVISE THE LIVE AND DEAD DESIGN LOADS. NOTE: SEE |
| TABLE 1607.1 FBC FOR THE MINIMUM UNIFORMLY DISTRIBUTED |
| LIVE LOADS AND MINIMUM CONCENTRATED LIVE LOADS AND |
| REVISE ALL LIVE LOADS ACCORDINGLY. |
| |
| C)ACCORDING TO SEC. 1609.4 FBC THIS BUILDING IS LOCATED |
| IN EXPOSURE "C" NOT EXPOSURE "B". REVISE AS REQUIRED |
| AND REVISE ALL COMPONENTS AND CLADDING DESIGN PRESSURES |
| ACCORDINGLY. NOTE: CONVERT THE ULTIMATE WIND LOADS VULT |
| TO NOMINAL WIND LOADS VASD FOR COMPONENTS AND CLADDING. |
| |
| D) PROVIDE COMPLETE WIND DESIGN CRITERIA AS REQUIRED BY |
| SEC. 1603.1.4 FBC. INCLUDE THE RISK CATEGORY (TABLE |
| 1604.5) AND APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| |
| E) COORDINATE CONSTRUCTION TYPE AND OCCUPANCY |
| CLASSIFICATION WITH SHEET G100. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 6- SHEET A-100: |
| A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING |
| THE ACCESSIBLE ROUTE SEC. 206 AND 502 FBC |
| ACCESSIBILITY. PROVIDE DIMENSIONS, REVISE ACCESS AISLE. |
| ETC. |
| |
| B) CLEARLY IDENTIFY THE PROPERTY LINES AND PROVIDE |
| DIMENSIONS. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| C) PROVIDE COMPLETE STRUCTURAL DETAILS AND |
| SPECIFICATIONS FOR ALL THE PROPOSED POST AND PANEL |
| CONCRETE WALL AND CORRUGATED ALUMINUM GATES SHOWN ON |
| THE SITE PLAN. COORDINATE WITH INFORMATION SHOWN ON |
| EXTERIOR ELEVATIONS AND SECTIONS. SEC. 106.1 FBC. |
| |
| 7- SHEET A-300: |
| A)PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING |
| THE ACCESSIBLE ROUTE SEC. 206.2.1 AND 402.2 FBC |
| ACCESSIBILITY. |
| |
| B)PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| CONSTRUCTION OF THE STAIRS SHOWING COMPLIANCE WITH LIVE |
| LOADS TABLE 1607.1 FBC. PROVIDE COMPLETE DIMENSIONS, |
| INCLUDING THE WIDTH IN ALL AREAS. SPECIFY TREADS AND |
| RISER DIMENSIONS TO SHOW COMPLIANCE WITH SEC. 1011.5.2 |
| FBC. |
| |
| C) PROVIDE HANDRAILS ON EACH SIDE OF THE STAIRWAY AS |
| REQUIRED BY SEC. 1011.11 FBC. |
| |
| D)PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS |
| FOR THE CONSTRUCTION OF THE ALUMINUM CANOPY ON THE EAST |
| WALL. SEC. 1601.1 FBC. |
| NOTE: CLEARLY SPECIFY HEADROOM. |
| |
| E) PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS |
| FOR THE ROOF HATCH OPENING. SEC. 1601.1 FBC. NOTE: |
| PROVIDE ROOF HATCH OPENING DIMENSIONS SHOWING |
| COMPLIANCE WITH SEC. 1011.12.2 FBC. |
| |
| 8- PROVIDE SECTION/DETAIL SHOWING COMPLIANCE WITH THE |
| HEADROOM BY THE DOOR TO THE OFFICE AREA FROM THE |
| WAREHOUSE AREA. SEC. 1208.2 FB. |
| |
| 9- ENERGY CALCULATIONS SUBMITTED: |
| A) ARCHITECT OF RECORD NEED TO SIGN AND PROVIDE |
| PROFESSIONAL LICENSE NUMBER AS REQUIRED BY SEC. |
| C103.1.1.1.2 FBC-ENERGY CONSERVATION. NOTE: ENVELOPE |
| INFORMATION SHOWN ON THE ENERGY CALCULATIONS IS NOT |
| PROVIDED ON THE PLANS SUBMITTED. FOR EXAMPLE CHECK THE |
| BELOW GRADE WALL, INSULATION, SLAB EDGE INFORMATION, |
| ETC. REVIEW ENERGY CALCULATIONS AND SIGN AS REQUIRED. |
| |
| B) ENERGY CALCULATIONS NEED TO BE CERTIFIED (SIGNED) BY |
| THE BUILDING OWNER OR ANY AUTHORIZED PERSONS AS |
| REQUIRED BY SEC. C103.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| 10- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.001 FOR: |
| (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| SUBMITTAL) |
| A) SWING ENTRY DOORS AS SHOWN ON PLANS. |
| |
| B) OVERHEAD DOORS AS SHOWN ON PLANS. |
| |
| C) ROOF HATCH AS SHOWN ON PLANS. |
| |
| D) PRECAST LINTELS AS SHOWN ON PLANS. |
| |
| E) PETERSEN ALUMINUM SIDING AS SHOWN ON PLANS. |
| |
| F) STOREFRONT WINDOWS AS SHOWN PLANS. NOTE: IDENTIFY |
| GLAZING/ MULLIONS. FOR ALL PRODUCTS WITH GLAZING, |
| PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF |
| GLAZING, MULLION INFORMATION IF REQUIRED, ATTACHMENTS |
| AND ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 |
| FBC-B 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL |
| BE INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURERS |
| INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| |
| G) ANY STRUCTURAL CONNECTORS SPECIFIED ON PLANS AND |
| SECTIONS. |
| |
| H) FLAT ROOF. AND CLEARLY MARK WHICH APPROVED ASSEMBLY |
| IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE |
| DESIGN PRESSURES OF SEC. 1609.1 FBC. NOTE: IF THE |
| SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES FOR |
| ALL ROOF ZONES, THEN SIGNED AND SEALED RAS 117 |
| CALCULATIONS ARE REQUIRED. |
| |
| 11- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4 CITY AMENDMENTS. |
| |
| 12- PROVIDE COMPLETE TRUSS PACKAGE (2 SIGNED AND SEALED |
| COPIES) REVIEWED AND APPROVED BY THE DESIGNER OF |
| RECORD. SEC. 107.3.4 CITY AMENDMENTS. |
| |
| 13- PERMIT FOR PROTECTION OF PEDESTRIANS BARRIER AND |
| COVERED WALKWAY WILL BE REQUIRED BY TABLE 3306.1 FBC |
| BEFORE CONSTRUCTION. |
| |
| 14- PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO HELP EXPEDITE THE REVIEW PROCESS. |
| ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY |
| REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS. |
| |
| |