Plan Review Notes
Plan Review Notes For Permit 18040834
Permit Number 18040834
Review Stop B
Sequence Number 1
Notes
Date Text
2018-05-03 18:41:53****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC B 1609, ALTHOUGH CALCULATIONS MAY SHOW THAT
 THREE FASTENERS ARE ADEQUATE, IT DOES NOT APPEAR
 ADEQUATE BASED ON THE SHAPE OF THE SIGN. ALSO, LOCATION
 OF FASTENERS WAS NOT SPECIFIED BUT IT APPEARS THAT THIS
 MAKES A DIFFERENCE.
  
 EITHER PROVIDE A PLAN SHOWING LOCATION OF FASTENERS
 (AND ADD ADDITIONAL AS NEEDED FOR THE SHAPE OF THE
 LETTERS), OR CONTACT ME TO DISCUSS.
  
  