2018-07-14 13:06:50 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| FBC R = FBC RESIDENTIAL |
| |
| 1. REVISE PLAN TO INCLUDE THE FOLLOWING INFORMATION: |
| |
| FBC B 705.3, BUILDINGS ON THE SAME LOT, SHOW DISTANCE |
| FROM PROPOSED SHED TO ASSUMED PROPERTY LINE (DISTANCE |
| FROM EX. RESIDENCE #325 TO ASSUMED PROPERTY LINE, |
| DISTANCE FROM PROPOSED STORAGE SHED TO ASSUMED PROPERTY |
| LINE, SHOW COMPLIANCE FOR BOTH STRUCTURES) |
| |
| PLAN SHOWS 6' BUT DOES NOT INCLUDE INFORMATION |
| REGARDING DISTANCE FROM EX. RESIDENCE #325 TO ASSUMED |
| PROPERTY LINE. |
| |
| SINCE THE PROPOSED STRUCTURE DOES NOT APPEAR TO HAVE |
| ANY OPENINGS ON THE SIDE FACING THE EXISTING STRUCTURE, |
| IT IS SUGGESTED THAT THE ASSUMED PROPERTY LINE BE |
| PLACED AT THE STRUCTURE TO GIVE MORE FLEXIBILITY FOR |
| SHOWING COMPLIANCE FOR THE EXISTING WOOD STRUCTURE (IF |
| PROPOSED CONSTRUCTION MEETS 2 HOUR REQUIREMENT). FOR |
| INSTANCE, SEE FBC B TABLE 705.8, TABLE 602. |
| |
| NOTE THAT BUILDING TYPE CAN BE DECLARED AS THE MINIMUM |
| REQUIRED BY CODE RATHER THAN ACTUAL CONSTRUCTION TYPE. |
| |
| SEE ALSO FBC B 705.3 EXCEPTION 1. |
| |
| PLEASE REVISE PLAN TO SHOW ANY FIRE RATINGS REQUIRED. |
| |
| PLEASE CONTACT ME IF YOU WISH TO DISCUSS. |
| |
| |